Juniper EX8208 Hardware Manual page 167

Hide thumbs Also See for EX8208:
Table of Contents

Advertisement

Table 68: Parts Required for Connecting an EX Series Switch to Earth Ground (continued)
Earthing
Terminal
Switch
Location
EX4200,
Left side of
EX4500,
the chassis
and
EX4550
EX6210
Rear panel of
the chassis (on
lower left
side)
EX8208
Left side of
the chassis
Grounding
Cable
Grounding Lug
Requirements
Specifications
14 AWG (2 mm²),
Panduit
minimum 90° C
LCC10-14BWL or
wire, or as
equivalent—
permitted by the
not provided
local code
The grounding
Panduit LCD2-14A-Q
cable must be
or equivalent
the same gauge
—provided
as the power
feed cables and
as permitted by
the local code.
6 AWG
Panduit LCD2-14A-Q
(13.3 mm²),
or equivalent
minimum 90° C
—provided
wire, or as
permitted by the
local code
Screws and
Additional
Washers
Information
Two 10-32
See
"Special
x .25 in. screws
Instructions to Follow
with #10
Before Connecting
split-lock
Earth Ground to an
washer—
EX Series Switch" on
not provided
page
169.
Two #10 flat
washers—
not provided
Two ¼ -20
x 0.5 in. screws
with #¼"
split-washer
—provided
Two #¼" flat
washers—
provided
Two ¼ -20
x 0.5 in. screws
with #¼"
split-washer
—provided
Two #¼" flat
washers—
provided