4.8.7 Swing Mode
For the textile and chemical fiber processing equipment, the swing function improves the
uniform density of traversing and winding, as shown in Figure 4-24. The function is set in
PB-00 to PB-04. For details, see the description of these function codes.
Figure 4-24 Swing function
Swing frequency running
PB-01 > 0%
PB-02: Jump frequency
amplitude
PB-03: Swing frequency
cycle
PB-04: Triangular wave
rising time coefficient
f
Pendulum
4.8.8 Multi-Speed Mode
In scenarios where the running frequency of the AC drive need not be adjusted continuously
and only several frequencies are required, the multi-speed control can be used. The
I5300 supports a maximum of 16 running frequencies, which are implemented by state
combinations of four DI terminals. Set the function codes corresponding to DI terminals to a
value among 12 to 15, and then the DI terminals are specified as the multi-frequency input
terminals. The multiple frequencies are set based on the multi-frequency table in group
PC. In addition, you need to set P0-03 (Main frequency source X selection) to 6 (Multi-
reference). The following figure shows how to set the multi-speed function.
Figure 4-25 Setting the multi-speed function
Terminal Function
code
P4-00
DI1
P4-01
DI2
0
P4-02
DI3
P4-03
DI4
0
P4-04
DI5
P4-05
DI6
P4-06
DI7
P4-07
DI8
0
P4-08
1
DI9
P4-09
DI10
In the preceding figure, DI7, DI4, DI8, and DI2 are used as the multi-frequency input
terminals, each of which has a bit value. The state combinations of these terminals
correspond to multiple frequencies, When (DI7, DI4, DI8, DI2) = (0, 0, 1, 0), the state
combination value is 2, corresponding to the value set in FC-02. The target running
frequency is automatically calculated by PC-02 x P0-10.
The I5300 supports a maximum of four DI terminals to be used as the multi-frequency
input terminals. You can also use less than four DI terminals, and the empty bit is considered
to be 0.
Reciprocating
motor
mechanism
t
(Binary )
State
Setting
combination
value
0 0 0 0
.
0 0 0 1
.
0 0 1 0
. .
.
1 1 1 0
.
1 1 1 1
.
15
14
13
12
..
Operation, Display and Application Example
With swing
frequency
Multi-frequency
table
%
PC-00
PC-01
PC-02
...
PC-14
PC-15
× (P0-10)
Maximum
frequency
source selection
- 65 -
Without swing
frequency
Winding motor rotates
at uniform linear speed
Select multi -reference as
the frequency source
P0-07 = 0
P0-27 = 0
P0-03 = 6
Target
Frequency
running
frequency