I5300 User Manual
Function Code
A1-03
A1-04
VDI1 to VDI5 have the same functions as DI terminals on the control board and can be used
for digital input. For more details, see description of P4-00 to P4-09.
Function Code
A1-05
VDI state setting mode
A1-06
VDI state selection
Different from DI terminals, VDI state can be set in two modes, selected in A1-05:
Decided by state of VDOx
Whether the state a VDI is valid is determined by the state of the corresponding VDO
and VDIx is uniquely bound to VDOx (x is between 1 and 5). For example, to implement
the function that the AC drive reports an alarm and stops when the AI1 input exceeds
the limit, perform the following setting:
1) Allocate VDI1 with function 44 "User-defined fault 1" (A1-00 = 44).
2) Set A1-05 to xxx0.
3) Allocate VDO1 with function 31 "AI1 input limit exceeded" (A1-11 = 31).
Parameter Name
VDI4 function selection
VDI5 function selection
Parameter Name
Description of Function Codes
Setting Range
0–59
0–59
Setting Range
Unit's digit (VDI1)
0: Decided by state of VDOx
1: Decided by A1-06
Ten's digit (VDI2)
0, 1 (same as VDI1)
Hundred's digit (VDI3)
0, 1 (same as VDI1)
Thousand's digit (VDI4)
0, 1 (same as VDI1)
Ten thousand's digit (VDI5)
0, 1 (same as VDI1)
Unit's digit (VDI1)
0: Invalid
1: Valid
Ten's digit (VDI2)
0, 1 (same as VDI1)
Hundred's digit (VDI3)
0, 1 (same as VDI1)
Thousand's digit (VDI4)
0, 1 (same as VDI1)
Ten thousand's digit (VDI5)
0, 1 (same as VDI1)
- 225 -
Default
0
0
Default
00000