Description of Function Codes
Figure 6-24 Any current reaching detection
Output
current
Any current
reaching
Any current reaching
detection signal
DO or relay
Function Code
P8-42
Timing function
P8-43
Timing duration source
P8-44
Timing duration
These parameters are used to implement the AC drive timing function.
If P8-42 is set to 1, the AC drive starts to time at startup. When the set timing duration is
reached, the AC drive stops automatically and meanwhile the corresponding DO becomes
ON.
The AC drive starts timing from 0 each time it starts up and the remaining timing duration
can be queried by U0-20.
The timing duration is set in P8-43 and P8-44, in unit of minute.
Function Code
P8-45
P8-46
These two parameters are used to set the limits of the input voltage to provide protection on
the AC drive. When the AI1 input is larger than the value of P8-46 or smaller than the value
of P8-45, the corresponding DO becomes ON, indicating that AI1 input exceeds the limit.
Function Code
P8-47
When the heatsink temperature of the AC drive reaches the value of this parameter, the
corresponding DO becomes ON, indicating that the module temperature reaches the
threshold.
ON
ON
OFF
Parameter Name
Parameter Name
AI1 input voltage lower limit
AI1 input voltage upper limit
Parameter Name
Module temperature threshold
Any current reaching amplitude
Any current reaching amplitude
ON
OFF
OFF
Setting Range
0: Disabled
1: Enabled
0: P8-44
1: AI1
2: AI2
3: AI3
(100% of analog input corresponds
to the value of P8-44)
0.0–6500.0 min
Setting Range
0.00 V to P8-46
P8-45 to 10.00 V
Setting Range
0–75 °C
- 196 -
I5300 User Manual
Default
0
0
0.0 min
Default
3.10 V
6.80 V
Default
75 °C