Function Code
P5-06
P5-07
P5-08
The output pulse frequency of the FMP terminal ranges from 0.01 kHz to "Maximum FMP
output frequency" (P5-09). The value of P5-09 is between 0.01 kHz and 100.00 kHz.
The output range of AO1 and AO2 is 0–10 V or 0–20 mA. The relationship between pulse
and analog output ranges and corresponding functions is listed in the following table.
Table 6-6 Relationship between pulse and analog output ranges and corresponding
functions
Value
0
Running frequency
1
Set frequency
2
Output current
3
Output torque (absolute value)
4
Output power
5
Output voltage
6
Pulse input
7
AI1
8
AI2
9
AI3
10
Length
11
Count value
12
Communication setting
13
Motor rotational speed
14
Output current
15
Output voltage
16
Output torque (actual value)
Function Code
P5-09
If the FM terminal is used for pulse output, this parameter is used to set the maximum
frequency of pulse output.
Parameter Name
FMP function selection
AO1 function selection
AO2 function selection
Function
Parameter Name
Maximum FMP output frequency
Description of Function Codes
Range (Corresponding to Pulse or Analog
Output Range 0.0%–100.0%)
0 to maximum output frequency
0 to maximum output frequency
0 to 2 times of rated motor current
0 to 2 times of rated motor torque
0 to 2 times of rated power
0 to 1.2 times of rated AC drive voltage
0.01–100.00 kHz
0–10 V
0–10 V (or 0–20 mA)
0–0 V
0 to maximum set length
0 to maximum count value
0.0%–100.0%
0 to rotational speed corresponding to
maximum output frequency
0.0–1000.0 A
0.0–000.0 V
-2 times of rated motor torque to 2 times of
rated motor torque
Setting Range
0.01–100.00 kHz
- 175 -
Default
0
0
1
Default
50.00 kHz