I5300 User Manual
Function Code
Input phase loss
protection/contactor
P9-12
energizing protection
selection
It is used to determine whether to perform input phase loss or contactor energizing
protection.
The I5300 models that provide this function are listed in the following table.
Table 6-8 I5300 models providing the input phase loss or contactor energizing protection
function
For every voltage class, the I5300 AC drives of powers equal to or greater than those
listed in the preceding table provide the function of input phase loss or contactor energizing
protection. The I5300 AC drives below the power listed in the table do not have the
function no matter whether P9-12 is set to 0 or 1.
Function Code
P9-13
It is used to determine whether to perform output phase loss protection.
Function Code
P9-14
P9-15
P9-16
It is used to record the types of the most recent three faults of the AC drive. 0 indicates no
fault. For possible causes and solution of each fault, refer to Chapter 8.
Function Code
P9-17
Frequency upon 3rd fault
P9-18
Current upon 3rd fault
P9-19
Bus voltage upon 3rd fault
Parameter Name
Voltage Class
Three-phase 380 V
Parameter Name
Output phase loss protection selection
Name
1st fault type
2nd fault type
3rd (latest) fault type
Parameter Name
Setting Range
Unit's digit: Input phase loss protection
Ten's digit: Contactor energizing
protection
0: Disabled
1: Enabled
Models
18.5 kW G model
It displays the frequency when the latest fault
occurs.
It displays the current when the latest fault
occurs.
It displays the bus voltage when the latest fault
occurs.
- 201 -
Description of Function Codes
Setting Range
0: Disabled
1: Enabled
Setting Range
0–99
Description
Default
11
Default
1