IACDRIVE I5300 Series User Manual page 194

Ac drive
Table of Contents

Advertisement

Description of Function Codes
Function Code
Any frequency reaching
P8-33
detection amplitude 2
If the output frequency of the AC drive is within the positive and negative amplitudes of the
any frequency reaching detection value, the corresponding DO becomes ON.
The I5300 provides two groups of any frequency reaching detection parameters, including
frequency detection value and detection amplitude, as shown in the following figure.
Figure 6-21 Any frequency reaching detection
Any frequency
Any frequency reaching
detection signal
DO or relay
Function Code
P8-34
Zero current detection level
P8-35
Zero current detection delay time
If the output current of the AC drive is equal to or less than the zero current detection level
and the duration exceeds the zero current detection delay time, the corresponding DO
becomes ON. The zero current detection is shown in the following figure.
Figure 6-22 Zero current detection
Parameter Name
Running frequency
reaching
ON
OFF
Parameter Name
Output current
Zero current
detection level
P8-34
Zero current
detection signal
Setting Range
0.0%–100.0% (maximum
frequency)
ON
OFF
OFF
Setting Range
0.0%–300.0% (rated
motor current)
0.00–600.00s
Zero current
detection delay time
P8-35
- 194 -
I5300 User Manual
Default
0.0%
Frequency reaching
detection amplitude
Frequency reaching
detection amplitude
Time
Default
5.0%
0.10s
Time
Time

Advertisement

Table of Contents
loading

Table of Contents