I5300 User Manual
Function
Parameter Name
Code
Module temperature
P8-47
threshold
P8-48
Cooling fan control
P8-49
Wakeup frequency
P8-50
Wakeup delay time
P8-51
Dormant frequency
P8-52
Dormant delay time
Current running time
P8-53
reached
Output power correction
P8-54
coefficient
Motor overload protection
P9-00
selection
Motor overload protection
P9-01
gain
Motor overload warning
P9-02
coefficient
P9-03
Overvoltage stall gain
Overvoltage stall protective
P9-04
voltage
P9-05
Overcurrent stall gain
Overcurrent stall protective
P9-06
current
Short-circuit to ground upon
P9-07
power-on
P9-09
Fault auto reset times
DO action during fault auto
P9-10
reset
Time interval of fault auto
P9-11
reset
Input phase loss protection/
P9-12
contactor energizing
protection selection
Setting Range
0–100°C
0: Fan working during running
1: Fan working continuously
Dormant frequency (P8-51) to
maximum frequency (P0-10)
0.0–6500.0s
0.00 Hz to wakeup frequency (P8-
49)
0.0–6500.0s
0.0–6500.0 min
0.00%–200 .0%
Group P9: Fault and Protection
0: Disabled
1: Enabled
0.20–10.00
50%–100%
0 (no stall overvoltage)–100
120%–150%
0–100
100%–200%
0: Disabled
1: Enabled
0–20
0: Not act
1: Act
0.1s–100.0s
Unit's digit: Input phase loss
protection
Ten's digit: Contactor energizing
protection
0: Disabled
1: Enabled
- 101 -
Function Code Table
Default
Property
75°C
☆
0
☆
0.00 Hz
☆
0.0s
☆
0.00 Hz
☆
0.0s
☆
0.0 min
☆
100.0%
☆
1
☆
1.00
☆
80%
☆
0
☆
130%
☆
20
☆
150%
☆
1
☆
0
☆
0
☆
1.0s
☆
11
☆