IACDRIVE I5300 Series User Manual page 214

Ac drive
Table of Contents

Advertisement

Description of Function Codes
Function Code
PB-03
Swing frequency cycle
PB-04
Triangular wave rising time coefficient
PB-03 specifes the time of a complete swing frequency cycle.
PB-04 specifies the time percentage of triangular wave rising time to PB-03 (Swing
frequency cycle).
Triangular wave rising time = PB-03 (Swing frequency cycle) x PB-04 (Triangular wave
rising time coefficient, unit: s)
Triangular wave falling time = PB-03 (Swing frequency cycle) x (1 – PB-04 Triangular
wave rising time coefficient ,unit: s)
Function Code
PB-05
Set length
PB-06
Actual length
PB-07
Number of pulses per meter
The preceding parameters are used for fixed length control.
The length information is collected by DI terminals. PB-06 (Actual length) is calculated by
dividing the number of pulses collected by the DI terminal by PB-07 (Number of pulses each
meter).
When the actual length PB-06 exceeds the set length in PB-05, the DO terminal allocated
with function 10 (Length reached) becomes ON.
During the fixed length control, the length reset operation can be performed via the DI
terminal allocated with function 28. For details, see the descriptions of P4-00 to P4-09.
Allocate corresponding DI terminal with function 27 (Length count input) in applications. If
the pulse frequency is high, DI5 must be used.
Function Code
PB-08
Set count value
PB-09
Designated count value
The count value needs to be collected by DI terminal. Allocate the corresponding DI terminal
with function 25 (Counter input) in applications. If the pulse frequency is high, DI5 must be
used.
When the count value reaches the set count value (PB-08), the DO terminal allocated with
function 8 (Set count value reached) becomes ON. Then the counter stops counting.
When the counting value reaches the designated counting value (PB-09), the DO terminal
allocated with function 9 (Designated count value reached) becomes ON. Then the counter
continues to count until the set count value is reached.
PB-09 should be equal to or smaller than PB-08.
Parameter Name
Parameter Name
Parameter Name
Setting Range
0.0–3000.0s
0.0%–100.0%
Setting Range
0–65535 m
0–65535 m
0.1–6553.5
Setting Range
1–65535
1–65535
- 214 -
I5300 User Manual
Default
10.0s
50.0%
Default
1000 m
0 m
100.0
Default
1000
1000