IACDRIVE I5300 Series User Manual page 204

Ac drive
Table of Contents

Advertisement

Description of Function Codes
Function Code Parameter Name
Fault protection
P9-49
action selection 3
Fault protection
P9-50
action selection 4
If "Coast to stop" is selected, the AC drive displays Err** and directly stops.
If "Stop according to the stop mode" is selected, the AC drive displays A** and stops
according to the stop mode. After stop, the AC drive displays Err**.
If "Continue to run" is selected, the AC drive continues to run and displays A**. The
running frequency is set in P9-54.
Function Code
Frequency selection
P9-54
for continuing to run
upon fault
Backup frequency
P9-55
upon abnormality
Unit's digit (User-defined fault 1, Err27)
Same as unit's digit in P9-47
Ten's digit (User-defined fault 2, Err28)
Same as unit's digit in P9-47
Hundred's digit (Accumulative power-on time
reached, Err29)
Same as unit's digit in P9-47
Thousand's digit (Load becoming 0, Err30)
0: Coast to stop
1: Stop according to the stop mode
2: Continue to run at 7% of rated motor frequency
and resume to the set frequency if the load
recovers
Ten thousand's digit (PID feedback lost during
running, Err31)
Same as unit's digit in P9-47
Unit's digit (Too large speed deviation, Err42)
Same as unit's digit in P9-47
Ten's digit (Motor over-speed, Err43)
Same as unit's digit in P9-47
Hundred's digit (Initial position fault, Err51)
Same as unit's digit in P9-47
Thousand's digit (Speed feedback fault, Err52)
Same as unit's digit in P9-47
Ten thousand's digit: Reserved
Parameter Name
Setting Range
Setting Range
0: Current running frequency
1: Set frequency
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon abnormality
0.0%–100.0% (maximum frequency)
- 204 -
I5300 User Manual
Default
00000
00000
Default
0
100.0%