IACDRIVE I5300 Series User Manual page 61

Ac drive
Table of Contents

Advertisement

I5300 User Manual
According to the preceding figure, the running frequency of the AC drive can be set by
means of function codes, manual adjustment, analog input, multi-speed terminal, external
feedback signal, internal PID regulator, or the host computer.
Set the corresponding function codes of each frequency setting mode, as shown in the
preceding figure.
4.8.2 Frequency Setting by the Auxiliary Frequency Source
The frequency setting by the auxiliary frequency source is the same as the frequency setting
by the main frequency source. You can set the auxiliary frequency source in P0-04.
Figure 4-18 Frequency set by the auxiliary frequency source
P0-08
AI1
0-10 V
0-10 V
AI2
4-20 mA
On the
extension
AI3
-10 V to 10 V
board
DI5
P4-04=30
P4-00 to P4-09
DI1-DI10
= 12/13/14/15
Group PC
AI1-AI2
Group PA
DI5 (f )
PD-00 to PD-05
Host
Communication
computer
configuration
The relationship between the target running frequency and the main frequency source and
auxiliary frequency source is set in P0-07, as follows:
1)
Main frequency source X: The main frequency source is directly used to set the target
running frequency.
2)
Auxiliary frequency source Y: The auxiliary frequency source is directly used to set the
target running frequency.
3)
X and Y operation: There are four operation methods, namely, X+Y, X-Y, maximum of X
and Y, and minimum of X and Y.
4)
Frequency switchover: A DI terminal is used to switch over between the preceding
three frequency setting channels.
0
Digital setting
Retentive at
1
power failure
2
P4-33
Analog
JP8
3
P4-33
Analog
4
P4-33
Analog
P4-29
5
Pulse
to P4-32
setting
PC-00 to PC-15
6
(each
Multi-speed
frequency )
7
Simple PLC
8
PID
9
H1000 register
Communication
setting
Operation, Display and Application Example
P0-04
P0-08
(Auxiliary
frequency
source Y)
P4-00 to P4-09
DI1 to DI10
- 61 -
Auxiliary
frequency
source Y
Frequency
switchover
= 40