Description of Function Codes
Function Code
P0-22
Frequency reference resolution
It is used to set the resolution of all frequency-related parameters.
If the resolution is 0.1 Hz, the I5300 can output up to 3200 Hz. If the resolution is 0.01 Hz,
the I5300 can output up to 600.00 Hz.
• Modifying this parameter will make the decimal places of all frequency-related parameters
change and corresponding frequency values change.
• This parameter is not resumed when factory setting is resumed.
Function Code
Retentive of digital setting
P0-23
frequency upon power failure
This parameter is valid only when the frequency source is digital setting.
If P0-23 is set to 0, the digital setting frequency value resumes to the value of P0-08 (Preset
frequency) after the AC drive stops. The modification by using keys
terminal UP/DOWN function is cleared.
If P0-23 is set to 1, the digital setting frequency value is the set frequency at the moment
when the AC drive stops. The modification by using keys
DOWN function remains effective.
Function Code
Motor parameter group
P0-24
selection
The I5300 can drive four motors at different time. You can set the motor nameplate
parameters respectively, independent motor auto-tuning, different control modes, and
parameters related to running performance respectively for the four motors.
Motor parameter group 1 corresponds to groups P1 and P2. Motor parameter groups 2, 3
and 4 correspond to groups A2, A3 and A4 respectively.
You can select the current motor parameter group by using P0-24 or perform switchover
between the motor parameter groups by means of a DI terminal. If motor parameters
selected by means of P0-24 conflict with those selected by means of DI terminal, the
selection by DI is preferred.
Parameter Name
Parameter Name
Parameter Name
Setting Range
1: 0.1 Hz
2: 0.01 Hz
Note
Setting Range
0: Not retentive
1: Retentive
and
Setting Range
0: Motor parameter group 1
1: Motor parameter group 2
2: Motor parameter group 3
3: Motor parameter group 4
- 146 -
I5300 User Manual
Default
2
Default
0
and
or the
or the terminal UP/
Default
0