Operation, Display and Application Examples
4.7.3 Stop Mode
The AC drive supports two stop modes, decelerate to stop and coast to stop, set in P6-10.
Figure 4-12 Diagram of two stop modes (decelerate to stop and coast to stop)
Frequency (f)
Running
P6-10 = 0: Decelerate to stop
frequency
P6-11 (Initial frequency of
stop DC braking)
Stop command
4.7.4 Timing Stop
The I5300 supports timing stop. This function is enabled by P8-42 and the timing duration
is determined by P8-43 and P8-44.
Figure 4-13 Setting of the timing stop function
Running state
P8-42 = 1 (timing function enabled )
P8-43 = 0 (timing duration determined by P8 - 44)
P8-44 (Timing duration )
Running
command
You can set the timing duration by means of analog input (such as potentiometer signal).
For details, see the description of P8-43.
P0-18
(Deceleration time)
P6-12 (Waiting
time of stop DC
braking)
P6-12 (Stop DC
No
braking time)
output
P6-13 (Stop DC
braking current, %)
Time (t)
Automatic stop
Frequency (f)
Running
frequency
Time (t)
Stop
command
Running state
P8-43 = 0 ( timing duration determined by P8-44)
Set P8-42 to 1 to enable the timing function .
Running
command
- 58 -
I5300 User Manual
P6-10 = 1: Coast to stop
Rotational speed under
load , coast to stop by
inertia
P8-44 (Timing duration )
Automatic stop
Time (t)
Time (t)

Advertisement