I5300 User Manual
Function Code
P8-36
P8-37
If the output current of the AC drive is equal to or higher than the overcurrent threshold and
the duration exceeds the detection delay time, the corresponding DO becomes ON. The
output overcurrent detection function is shown in the following figure.
Figure 6-23 Output overcurrent detection
Output overcurrent
threshold
Output overcurrent
detection signal
Function Code
P8-38
Any current reaching 1
Any current reaching 1
P8-39
amplitude
P8-40
Any current reaching 2
Any current reaching 2
P8-41
amplitude
If the output current of the AC drive is within the positive and negative amplitudes of any
current reaching detection value, the corresponding DO becomes ON.
The I5300 provides two groups of any current reaching detection parameters, including
current detection value and detection amplitudes, as shown in the following figure.
Parameter Name
Output overcurrent threshold
Output overcurrent detection
delay time
Output
current
P8-36
Parameter Name
Description of Function Codes
Setting Range
0.0% (no detection)
0.1%–300.0% (rated
motor current)
0.00–600.00s
Output overcurrent
detection delay time
P8-37
Setting Range
0.0%–300.0% (rated motor current)
0.0%–300.0% (rated motor current)
0.0%–300.0% (rated motor current)
0.0%–300.0% (rated motor current)
- 195 -
Default
200.0%
0.00s
Time
Time
Default
100.0%
0.0%
100.0%
0.0%