Function Code
Acceleration/Deceleration
P0-25
time base frequency
The acceleration/deceleration time indicates the time for the AC drive to increase from 0
Hz to the frequency set in P0-25. If this parameter is set to 1, the acceleration/deceleration
time is related to the set frequency. If the set frequency changes frequently, the motor's
acceleration/deceleration also changes.
Function Code
Base frequency for UP/DOWN
P0-26
modification during running
This parameter is valid only when the frequency source is digital setting.
It is used to set the base frequency to be modified by using keys
terminal UP/DOWN function. If the running frequency and set frequency are different, there
will be a large difference between the AC drive's performance during the acceleration/
deceleration process.
Function Code
Parameter Name
Binding command
P0-27
source to
frequency source
It is used to bind the three running command sources with the nine frequency sources,
facilitating to implement synchronous switchover.
For details on the frequency sources, see the description of P0-03 (Main frequency source X
selection). Different running command sources can be bound to the same frequency source.
Parameter Name
Parameter Name
Unit's digit (Binding operation panel
command to frequency source)
0: No binding
1: Frequency source by digital setting
2: AI1
3: AI2
4: AI3
5: Pulse setting (DI5)
6: Multi-reference
7: Simple PLC
8: PID
9: Communication setting
Ten's digit (Binding terminal command to
frequency source)
0–9, same as unit's digit
Hundred's digit (Binding communication
command to frequency source)
0–9, same as unit's digit)
Description of Function Codes
Setting Range
0: Maximum frequency (P0-10)
1: Set frequency
2: 100 Hz
Setting Range
0: Running frequency
1: Set frequency
Setting Range
- 147 -