In different applications, 100% of analog input corresponds to different nominal values. For
details, refer to the description of different applications.
Two typical setting examples are shown in the following figure.
Figure 6-11 Corresponding relationship between analog input and set values
Function Code
P4-18
AI curve 2 minimum input
Corresponding setting of AI
P4-19
curve 2 minimum input
P4-20
AI curve 2 maximum input
Corresponding setting of AI
P4-21
curve 2 maximum input
P4-22
AI2 filter time
Function Code
P4-23
AI curve 3 minimum input
Corresponding setting of AI
P4-24
curve 3 minimum input
P4-25
AI curve 3 maximum input
Corresponding setting of AI
P4-26
curve 3 maximum input
P4-27
AI3 filter time
The method of setting AI2 and AI3 functions is similar to that of setting AI1 function.
Corresponding set value
(frequency, torque)
100.0%
0 V (0 mA)
Corresponding set value
(frequency, torque)
100.0%
0 V (0 mA)
-100.0%
Parameter Name
Parameter Name
Description of Function Codes
AI
10 V (20 mA)
AI
10 V (20 mA)
Setting Range
0.00 V to P4-20
-100.00%–100.0%
P4-18 to 10.00 V
-100.00%–100.0%
0.00–10.00s
Setting Range
0.00 V to P4-25
-100.00%–100.0%
P4-23 to 10.00 V
-100.00%–100.0%
0.00–10.00s
- 169 -
Default
0.00 V
0.0%
10.00 V
100.0%
0.10s
Default
0.00 V
0.0%
10.00 V
100.0%
0.10s