IACDRIVE I5300 Series User Manual page 192

Ac drive
Table of Contents

Advertisement

Description of Function Codes
Function Code
Jump frequency during
P8-22
acceleration/deceleration
It is used to set whether the jump frequencies are valid during acceleration/deceleration.
When the jump frequencies are valid during acceleration/deceleration, and the running
frequency is within the frequency jump range, the actual running frequency will jump over
the set frequency jump amplitude (rise directly from the lowest jump frequency to the highest
jump frequency). The following figure shows the diagram when the jump frequencies are
valid during acceleration/deceleration.
Figure 6-19 Diagram when the jump frequencies are valid during acceleration/deceleration
Output
frequency (Hz)
frequency 2
frequency 1
Function Code
Frequency switchover point between
P8-25
acceleration time 1 and acceleration time 2
Frequency switchover point between
P8-26
deceleration time 1 and deceleration time 2
This function is valid when motor 1 is selected and acceleration/deceleration time switchover
is not performed by means of DI terminal. It is used to select different groups of acceleration/
deceleration time based on the running frequency range rather than DI terminal during the
running process of the AC drive.
Parameter Name
Jump
Jump
Frequency jump amplitude
Frequency jump amplitude
Parameter Name
Setting Range
0: Disabled
1: Enabled
Frequency jump amplitude
Frequency jump amplitude
Frequency jump amplitude
Frequency jump amplitude
Time (t)
Setting Range
0.00 Hz to maximum
frequency
0.00 to maximum
frequency
- 192 -
I5300 User Manual
Default
0
Default
0.00 Hz
0.00 Hz

Advertisement

Table of Contents
loading

Table of Contents