I5300 User Manual
These two parameters are respectively used to set the detection value of output frequency
and hysteresis value upon cancellation of the output. The value of P8-20 is a percentage of
the hysteresis frequency to the frequency detection value (P8-19).
The FDT function is shown in the following figure.
Figure 6-17 FDT level
Function Code
P8-21
If the AC drive running frequency is within the certain range of the set frequency, the
corresponding DO terminal becomes ON.
This parameter is used to set the range within which the output frequency is detected
to reach the set frequency. The value of this parameter is a percentage relative to the
maximum frequency. The detection range of frequency reached is shown in the following
figure.
Figure 6-18 Detection range of frequency reached
Output frequency (Hz)
Frequency reached
Output frequency (Hz)
FDT level
Frequency reached
detection signal
(DO, relay)
Parameter Name
Detection range of frequency
reached
Set frequency
detection signal
ON
Description of Function Codes
FDT hysteresis
= P8-19 x P8-20
Time (t)
ON
Time (t)
Setting Range
0.00–100% (maximum
frequency)
Time (t)
ON
- 191 -
Default
0.0%
Detection
range