Advertisement

Description of Function Codes
Figure 6-25 Diagram of the overcurrent stall protection function
Overcurrent stall
protective current
Function Code
P9-07
It is used to determine whether to check the motor is short-circuited to ground at power-on
of the AC drive. If this function is enabled, the AC drive's UVW will have voltage output a
while after power-on.
Function Code
P9-09
It is used to set the times of fault auto resets if this function is used. After the value is
exceeded, the AC drive will remain in the fault state.
Function Code
P9-10
It is used to decide whether the DO acts during the fault auto reset if the fault auto reset
function is selected.
Function Code
P9-11
It is used to set the waiting time from the alarm of the AC drive to fault auto reset.
Output
current
Output
frequency
(Hz)
Set
frequency
Acceleration
process
Parameter Name
Short-circuit to ground upon power-
on
Parameter Name
Fault auto reset times
Parameter Name
DO action during fault auto reset
Parameter Name
Time interval of fault auto reset
Constant-
Deceleration
speed process
process
Setting Range
0: Disabled
1: Enabled
Setting Range
Setting Range
0: Not act
1: Act
Setting Range
0.1s–100.0s
- 200 -
I5300 User Manual
Time (t)
Time (t)
Default
Default
0–20
Default
0
Default
1.0s
1
0