Function Code Table
Function
Parameter Name
Code
Fault protection
P9-47
action selection 1
Fault protection
P9-48
action selection 2
Fault protection action
P9-48
selection 2
Setting Range
Unit's digit (Motor overload, Err11)
0: Coast to stop
1: Stop according to the stop
mode
2: Continue to run
Ten's digit (Power input phase
loss, Err12)
Same as unit's digit
Hundred's digit (Power output
phase loss, Err13)
Same as unit's digit
Thousand's digit (External
equipment fault, Err15)
Same as unit's digit
Ten thousand's digit
(Communication fault, Err16)
Same as unit's digit
Unit's digit (Encoder fault, Err20)
0: Coast to stop
1: Switch over to V/F control, stop
according to the stop mode
2: Switch over to V/F control,
continue to run
Ten's digit (EEPROM read-write
fault, Err21)
0: Coast to stop
1: Stop according to the stop
mode
Hundred's digit: reserved
Thousand's digit (Motor overheat,
Err25)
Same as unit's digit in P9-47
Ten thousand's digit
(Accumulative running time
reached)
Same as unit's digit in P9-47
- 104 -
I5300 User Manual
Default
Property
00000