I5300 User Manual
Function Code
Parameter Name
Command
P0-02
source selection
It is used to determine the input channel of the AC drive control commands, such as run,
stop, forward rotation, reverse rotation and jog operation. You can input the commands in
the following three channels:
0: Operation panel control ("LOCAL/REMOT" indicator off)
Commands are given by pressing keys
1: Terminal control ("LOCAL/REMOT" indicator on)
Commands are given by means of multifunctional input terminals with functions such
as FWD, REV, JOGF, and JOGR.
2: Communication control ("LOCAL/REMOT" indicator blinking)
Commands are given from host computer. If this parameter is set to 2, a communication
card (Modbus RTU, PROFIBUS-DP card, CANlink card, user programmable card or
CANopen card) must be installed.
If a PROFIBUS-DP card is selected and PZD1 data is valid, commands are given
by means of PZD1 data.
If a user programmable card is selected, commands are written to A7-08 by
means of the programmable card.
If any other card is selected, commands are written by means of the
communication address 0x2000.
Function Code
Parameter Name
Main frequency
P0-03
source X selection
Setting Range
0: Operation panel control (LED off)
1: Terminal control (LED on)
2: Communication control (LED blinking)
STOP
and
RUN
Setting Range
0: Digital setting (non-retentive at power
failure)
1: Digital setting (retentive at power failure)
2: AI1
3: AI2
4: AI3
5: Pulse setting (DI5)
6: Multi-reference
7: Simple PLC
8: PID
9: Communication setting
- 137 -
Description of Function Codes
on the operation panel.
RES
Default
0
Default
0