IACDRIVE I5300 Series User Manual page 167

Ac drive
Table of Contents

Advertisement

I5300 User Manual
As shown in the preceding figure, if K1 is ON, the AC drive instructs forward rotation
when K2 is OFF, and instructs reverse rotation when K2 is ON. If K1 is OFF, the AC
drive stops.
2: Three-line mode 1
In this mode, DI3 is RUN enabled terminal, and the direction is decided by DI1 and DI2.
The parameters are set as below:
Function Code
P4-11
P4-00
P4-01
P4-02
Figure 6-9 Setting of three-line mode 1
As shown in the preceding figure, if SB1 is ON, the AC drive instructs forward rotation
when SB2 is pressed to be ON and instructs reverse rotation when SB3 is pressed to
be ON. The AC drive stops immediately after SB1 becomes OFF. During normal startup
and running, SB1 must remain ON. The AC drive's running state is determined by the
final actions on SB1, SB2 and SB3.
3: Three-line mode 2
In this mode, DI3 is RUN enabled terminal. The RUN command is given by DI1 and the
direction is decided by DI2. The parameters are set as below:
Function Code
P4-11
P4-00
P4-01
P4-02
Parameter Name
Terminal command mode
DI1 function selection
DI2 function selection
DI3 function selection
Forward
SB2
button
Stop
SB1
button
Reverse
SB3
button
Parameter Name
Terminal command mode
DI1 function selection
DI2 function selection
DI3 function selection
Description of Function Codes
Value
2
1
2
3
Forward RUN (FWD)
DI1
DI3 RUN enabled
DI2
Reverse RUN (REV)
COM Digital common
Value
3
Three-line 2
1
RUN enabled
2
Forward or reverse direction
3
Three-line control
- 167 -
Function Description
Three-line 1
Forward RUN (FWD)
Reverse RUN (REV)
Three-line control
Function Description

Advertisement

Table of Contents
loading

Table of Contents