Description of Function Codes
When the AI1 input exceeds the limit, VDO1 becomes ON. At this moment, VDI1
becomes ON and the AC drive receives you-defined fault 1. Then the AC drive reports
Err27 and stops.
Decided by A1-06
The VDI state is determined by the binary bit of A1-06. For example, to implement
the function that the AC drive automatically enters the running state after power-on,
perform the following setting:
1)
Allocate VDI1 with function 1 "Forward RUN (FWD)" (A1-00 = 1).
2)
Set A1-05 to xxx1: The state of VDI1 is decided by A1-06.
3)
Set A1-06 to xxx1: VDI1 is valid.
4)
Set P0-02 to 1: The command source to terminal control.
5)
Set P8-18 to 0: Startup protection is not enabled.
When the AC drive completes initialization after power-on, it detects that VDI1 is valid
and VDI1 is allocated with the function of forward RUN. That is, the AC drive receives
the forward RUN command from the terminal. Therefore, The AC drive starts to run in
forward direction.
Function Code
A1-07
Function selection for AI1 used as DI 0–59
A1-08
Function selection for AI2 used as DI 0–59
A1-09
Function selection for AI3 used as DI 0–59
A1-10
State selection for AI used as DI
The functions of these parameters are to use AI as DI. When AI is used as DI, the AI state
is high level if the AI input voltage is 7 V or higher and is low level if the AI input voltage is 3
V or lower. The AI state is hysteresis if the AI input voltage is between 3 V and 7 V. A1-10 is
used to determine whether high level valid or low level valid when AI is used as DI.
The setting of AIs (used as DI) function is the same as that of DIs. For details, see the
descriptions of group P4.
The following figure takes AI input voltage as an example to describe the relationship
between AI input voltage and corresponding DI state.
Parameter Name
- 226 -
I5300 User Manual
Setting Range
Unit's digit (AI1)
0: High level valid
1: Low level valid
Ten's digit (AI2)
0, 1 (same as unit's digit)
Hundred's digit (AI3)
0, 1 (same as unit's digit)
Default
0
0
0
000