4.7.5 JOG Running
In certain applications, the AC drive needs to run in low speed temporarily to facilitate
equipment test or other commissioning operations. In this case, you can set the AC drive to
perform JOG running.
Figure 4-14 JOG running
Output
frequency
Actual
acceleration time
Set
acceleration time
JOG
command
Parameter Setting and Operation of JOG Running in Operation Panel Control
Figure 4-15 JOG running in operation panel control
JOG
command key
(stop state)
MF.K
Set the parameters according to the preceding figure. In stop state of the AC drive, hold
down
, and the AC drive starts JOG running. After you release
MF.K
decelerates to stop.
To perform reverse JOG, set P7-01 to 4 and F8-13 to 1. Hold down
drive starts reverse JOG running.
Acceleration /Deceleration
base frequency (P0-25)
frequency (P0-08)
JOG acceleration
time (P8-01)
Define the MF.K key
as the "Forward
Operation
JOG" key
panel control
P7-01 = 3
P0-02 = 0
Operation, Display and Application Example
JOG running
JOG deceleration
time (P8-02)
JOG running
parameters
JOG running frequency )
P8-00 (
JOG acceleration time)
P8-01 (
JOG deceleration time)
P8-02 (
- 59 -
Time (t)
Actual
deceleration time
Set
deceleration time
Forward
JOG
, the AC drive
MF.K
and the AC
MF.K