I. SPECIFICATIONS
Model:
Sensor Electronics Corporation SEC MILLENIUM Infrared Hydrocarbon Gas Detector
Available gases:
Methane
Hexane
Ethane
Diesel
Ethylene
Gasoline
Ethylene Oxide
Green Earth
Propane
DF 2000
Please note that this list is not all-inclusive.
hydrocarbons, provided a calibration gas is available.
Corporation.
Part Number: 1420280
Detection Method:
Diffusion
Optional sample draw (requires a minimum of 1 liter per minute flow rate)
Output (analog):
4-20 mA (Source type), max. 1000 Ohm load at 24 VDC supply voltage
Response Time:
T50 < 5 seconds
T90 < 10 seconds
Construction:
316 stainless steel.
Accuracy:
+/- 3% LFL, 0 to 50% LFL (Lower Flammable Limit)
+/- 5% LFL, 51 to 100% LFL
Operating Temperature Rating:
-40° to +70°C at 0 to 99% RH (non-condensing)
Operating Voltage:
24 VDC
Operating range: 18 to 32 VDC measured at the detector head
Power Consumption: 5 Watts Max.
Max. Current Draw: (at 24 VDC)
Average: 210 mA
Peak: 400 mA
Approvals:
Explosion Proofness:
Combustible Gas Performance: C22.2 No 152, ANSI/ISA 12.13.01 – 2000; (CSA)
Installation Category: Cat. I, Pollution Degree 2
Doc#: 1460002, Rev C
Jet A
Ethanol
Methanol
Butane
Hexane
Class I, Division 1, Groups B,C and D, Temp T5; (CSA for -40C to +50C)
UL 2075, Methane 0-100%LEL Only; (Conforms to UL2075, Intertek Listed)
(UL2075 Listing requires the use of the SEC3120 Transmitter.)
Operation Manual, SEC Millenium Hydrocarbon Gas Detector
Toluene
P-Xylene
Tert-Butyl Acetate
MEK
The SEC MILLENIUM can be calibrated for most
For more please contact Sensor Electronics
Page 5 of 14