Dust can be removed using compressed air. Hard or oily deposits can be removed using Isopropyl alcohol
and cotton tipped swabs. Wipe any film or residue left by the alcohol on the windows with a clean dry cotton
swab. The internal electro-polished wave-guide tube can be cleaned the same way. Be careful not to leave
any particles of the cleaning swab in the waveguide. The waveguide holes can collect pieces of the cleaning
swab.
After reassembling the unit (the waveguide and collar should be very tight to both ends of the SEC 5000
IREvolution housing. Once the unit is completely reassembled and power is reapplied, the SEC 5000
IREvolution must then be Zero calibrated. Refer to the calibration section of this manual.
If the fault doesn't clear, contact the factory.
! Warning: The SEC 5000 IR Evolution detector's flameproof joints are not intended to be repaired.
VI. Parts List
Part Number
142-2188
142-2409
142-2408
Description
Replacement Hydrophobic Filter
Wave Guide Tube
Wave Guide Tube Collar
Part Number 1460005
Revision C