Parameters: 15-** Main Menu - Drive Information - Danfoss VLT FC 102 Programming Manual

Hvac drive, software version 5.41
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Parameter Descriptions
3.15 Parameters: 15-** Main Menu - Drive
Information
Parameter group containing frequency converter
information such as operating data, hardware configu-
ration, and software versions.
3.15.1 15-0* Operating Data
15-00 Operating hours
Range:
Function:
0 h
[0 -
View how many hours the
*
2147483647 h]
frequency converter has run. The
value is saved when the frequency
converter is turned off.
15-01 Running Hours
Range:
Function:
0 h
[0 -
View how many hours the motor
*
2147483647 h]
has run. Reset the counter in
parameter 15-07 Reset Running
Hours Counter. The value is saved
when the frequency converter is
turned off.
15-02 kWh Counter
Range:
Function:
0 kWh
[0 -
Register the power consumption of
*
2147483647
the motor as an average value over
kWh]
1 hour. Reset the counter in
parameter 15-06 Reset kWh Counter.
15-03 Power Up's
Range:
Function:
0
[0 -
View the number of times the
*
2147483647 ]
frequency converter has been
powered up.
15-04 Over Temp's
Range:
Function:
0
[0 - 65535 ]
View the number of frequency
*
converter temperature faults.
15-05 Over Volt's
Range:
Function:
0
[0 - 65535 ]
View the number of frequency
*
converter overvoltages.
15-06 Reset kWh Counter
Option:
Function:
[0]
Do not reset
No reset of the kWh counter is
*
required.
M0010001
Programming Guide
15-06 Reset kWh Counter
Option:
[1]
15-07 Reset Running Hours Counter
Option:
[0]
*
[1]
15-08 Number of Starts
Range:
0
*
3.15.2 15-1* Data Log Settings
The data log enables continuous logging of up to 4 data
sources (parameter 15-10 Logging Source) at individual rates
(parameter 15-11 Logging Interval). A trigger event
(parameter 15-12 Trigger Event) and window
(parameter 15-14 Samples Before Trigger) are used to start
and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option:
[0]
*
[15]
[1397]
[1398]
[1399]
[1600]
Danfoss A/S © 10/2019 All rights reserved.
Function:
Reset counter
Press [OK] to reset the kWh counter
to 0 (see parameter 15-02 kWh
Counter).
Function:
Do not reset
No reset of the running hours
counter is required.
Reset counter
Select [1] Reset counter and press
[OK] to reset the running hours
counter (parameter 15-01 Running
Hours) and parameter 15-08 Number
of Starts to 0 (see also
parameter 15-01 Running Hours).
Function:
NOTICE
[0 -
2147483647 ]
This parameter is reset when
resetting parameter 15-07 Reset
Running Hours Counter.
This is a readout parameter only.
The counter shows the number of
starts and stops caused by a normal
start/stop command and/or when
entering/leaving sleep mode.
Function:
Select which variables are to be
logged.
None
Readout:
actual setup
Alert Alarm
Word
Alert Warning
Word
Alert Status
Word
Control Word
3
3
157