Parameter Descriptions
13-97 Alert Alarm Word
Range:
0
*
4294967295 ]
3
3
13-98 Alert Warning Word
Range:
0
*
4294967295 ]
13-99 Alert Status Word
Range:
0
*
4294967295 ]
3.14 Parameters: 14-** Main Menu - Special
Functions
14-00 Switching Pattern
Option:
[0]
60 AVM
[1]
SFAVM
14-01 Switching Frequency
Option:
[0]
1.0 kHz
[1]
1.5 kHz
[2]
2.0 kHz
[3]
2.5 kHz
[4]
3.0 kHz
[5]
3.5 kHz
[6]
4.0 kHz
[7]
5.0 kHz
146
Function:
[0 -
Shows the alarm word of a user-
defined alarm in hex code.
Function:
[0 -
Shows the warning word of a user-
defined alarm in hex code.
Function:
[0 -
Shows the status word of a user-
defined alarm in hex code.
Function:
Select the switching pattern: 60°
AVM or SFAVM.
Function:
Select the inverter switching
frequency. Changing the switching
frequency can help reduce acoustic
noise from the motor.
NOTICE
The output frequency value of
the frequency converter must
never exceed 1/10 of the
switching frequency. When the
motor is running, adjust the
switching frequency in
parameter 14-01 Switching
Frequency until the motor is as
noiseless as possible. See also
parameter 14-00 Switching
Pattern. For information about
derating, see the relevant
design guide.
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
HVAC Drive FC 102
14-01 Switching Frequency
Option:
[8]
[9]
[10]
[11]
[12]
[13]
[14]
14-03 Overmodulation
Option:
[0]
*
[1]
14-04 Acoustic Noise Reduction
Option:
[0]
*
[1]
3.14.1 14-1* Mains On/Off
Parameters for configuring mains failure monitoring and
handling.
14-10 Mains Failure
Option:
Function:
6.0 kHz
7.0 kHz
8.0 kHz
10.0 kHz
12.0kHz
14.0 kHz
16.0kHz
Function:
Off
Selects no overmodulation of the
output voltage to avoid torque
ripple on the motor shaft.
On
The overmodulation function
generates an extra voltage of up to
8% of U
output voltage without
max
overmodulation. This extra voltage
results in an extra torque of 10–
12% in the middle of the oversyn-
chronous range (from 0% at
nominal speed, rising to approxi-
mately 12% at double nominal
speed).
Function:
Off
No change of the acoustic motor
switching noise.
On
Select to reduce the acoustic noise
from the motor.
Function:
Select the function at which the
frequency converter must act, when
the threshold set in
parameter 14-11 Mains Fault Voltage
Level has been reached or a mains
failure inverse command is
activated via 1 of the digital inputs
(parameter group 5-1* Digital Inputs).
Only selection [0] No function, [3]
Coasting, or [6] Alarm is available
when parameter 1-10 Motor
Construction is set to [1] PM non-
salient SPM.