Parameter Descriptions
0-67 Bus Access Password
Range:
Function:
0
[0 - 9999 ]
Use this parameter to unlock the
*
frequency converter via fieldbus or
MCT 10 Set-up Software.
3.2.11 0-7* Clock Settings
Set the time and date of the internal clock. The internal
clock can be used for timed actions, energy log, trend
analysis, date/time stamps on alarms, logged data,
preventive maintenance, and so on.
It is possible to program the clock for daylight saving time/
summertime, weekly working days/non-working days
including 20 exceptions (holidays, and so on). Although the
clock settings can be set via the LCP, they can also be set
along with timed actions and preventative maintenance
functions using the MCT 10 Set-up Software tool.
NOTICE
The frequency converter has no back-up of the clock
function and the set date/time resets to default
(2000-01-01 00:00) after a power-down unless a real-time
clock-module with back-up is installed. If no module with
back-up is installed, only use the clock function if the
frequency converter is integrated into the BMS using
serial communications, with the BMS maintaining
synchronization of control equipment clock times. In
parameter 0-79 Clock Fault, it is possible to program for a
warning if the clock has not been set properly, for
example after a power down.
NOTICE
®
If mounting VLT
Analog I/O Option MCB 109, a battery
back-up of the date and time is included.
0-70 Date and Time
Range:
Function:
Size
[ 0 - 0 ]
Sets the date and time of the
related
internal clock. The format to be
*
used is set in parameter 0-71 Date
Format and parameter 0-72 Time
Format.
When using the VLT
Clock MCB 117 option, the time is
synchronized at 15:00 every day.
0-71 Date Format
Option:
Function:
Sets the date format to be used in
the LCP.
[0]
YYYY-MM-DD
[1]
DD-MM-YYYY
[2]
MM/DD/YYYY
M0010001
Programming Guide
0-72 Time Format
Option:
[0]
[1]
0-73 Time Zone Offset
Range:
0 min
*
0-74 DST/Summertime
Option:
[0]
*
[2]
0-76 DST/Summertime Start
Range:
Size
related
*
0-77 DST/Summertime End
Range:
Size
related
*
0-79 Clock Fault
Option:
®
Real-time
[0]
[1]
Danfoss A/S © 10/2019 All rights reserved.
Function:
Sets the time format to be used in
the LCP.
24 h
12 h
Function:
[-780 - 780
Enter the time zone offset relative
min]
to UTC. This parameter is required
for the automatic daylight saving
time adjustment.
Function:
Select how to handle daylight
saving time/summer time. For
manual setting of DST/summer
time, enter the start date and end
date in parameter 0-76 DST/
Summertime Start and
parameter 0-77 DST/Summertime
End.
Off
Manual
Function:
[ 0 - 0 ]
Sets the date and time when DST/
summer time starts. The date is
programmed in the format selected
in parameter 0-71 Date Format.
Function:
[ 0 - 0 ]
Sets the date and time when DST/
summer time ends. The date is
programmed in the format selected
in parameter 0-71 Date Format.
Function:
Enables or disables the clock
warning when the clock has not
been set, or has been reset due to
a power-down and no back-up is
®
installed. If VLT
MCB 109 is installed, [1] Enabled is
default.
Disabled
Enabled
3
Analog I/O Option
47