Parameter Descriptions
3-17 Reference 3 Source
Option:
[0]
No function
*
[1]
Analog Input
53
3
3
[2]
Analog Input
54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
Digital
pot.meter
[21]
Analog input
X30/11
[22]
Analog input
X30/12
[23]
Analog Input
X42/1
[24]
Analog Input
X42/3
[25]
Analog Input
X42/5
[29]
Analog Input
X48/2
[30]
Ext. Closed
Loop 1
[31]
Ext. Closed
Loop 2
[32]
Ext. Closed
Loop 3
[37]
Analog Input
X49/1
[38]
Analog Input
X49/3
[39]
Analog Input
X49/5
[133]
Fieldbus REF 1
3-19 Jog Speed [RPM]
Range:
Size
related
RPM]
*
78
Function:
Function:
[ 0 - par. 4-13
Enter a value for the jog speed
n
, which is a fixed output speed.
JOG
The frequency converter runs at
this speed when the jog function is
activated. The maximum limit is
defined in parameter 4-13 Motor
Speed High Limit [RPM].
See also parameter 3-11 Jog Speed
[Hz] and parameter 3-80 Jog Ramp
Time.
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
HVAC Drive FC 102
3.5.3 3-4* Ramp 1
Configure the ramp times for each of the 2 ramps
(parameter group 3-4* Ramp 1 and parameter group 3-5*
Ramp 2).
Illustration 3.21 Ramp 1
Option:
[0]
*
[1]
[2]
RPM
P 4-13
High-limit
Reference
P 1-25
Motor
speed
P 4-11
Low limit
P 3-*1
Ramp (X)Up
Time (Acc)
t
acc
Function:
NOTICE
If [1] S-ramp Const Jerk is
selected and the reference
during ramping is changed,
the ramp time may be
prolonged to realize a jerk-free
movement, which may result
in a longer start or stop time.
Extra adjustment of the S-
ramp ratios or switching
initiators may be necessary.
Select the ramp type, depending on
requirements for acceleration/
deceleration.
A linear ramp gives constant
acceleration during ramping. An S-
ramp gives non-linear acceleration,
compensating for jerk in the
application.
Linear
S-ramp Const
Acceleration with lowest possible
Jerk
jerk.
S-ramp Const
S-ramp based on the values set in
Time
parameter 3-41 Ramp 1 Ramp Up
Time and parameter 3-42 Ramp 1
Ramp Down Time.
Time
P 3-*2
Ramp (X)
Down
Time (Dec)
t
dec
M0010001