Danfoss VLT FC 102 Programming Manual page 109

Hvac drive, software version 5.41
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Parameter Descriptions
6-02 Fire Mode Live Zero Timeout Function
Option:
Function:
Select the timeout function when
fire mode is active. The function set
in this parameter is activated if the
input signal on analog inputs is
lower than 50% of the low value for
a time period defined in
parameter 6-00 Live Zero Timeout
Time.
[0]
Off
*
[1]
Freeze output
Frozen at the present value.
[2]
Stop
Overruled to stop.
[3]
Jogging
Overruled to jog speed.
[4]
Max. speed
Overruled to maximum speed.
3.8.2 6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog
input 1 (terminal 53).
6-10 Terminal 53 Low Voltage
Range:
Function:
NOTICE
0.07 V
[ 0 - par. 6-11
*
V]
For the live zero alarms to
work, parameter 6-10 Terminal
53 Low Voltage must have a
value of 1 V or greater.
Enter the low voltage value. This
analog input scaling value should
correspond to the low reference
feedback value set in
parameter 6-14 Terminal 53 Low Ref./
Feedb. Value.
6-11 Terminal 53 High Voltage
Range:
Function:
10 V
[ par. 6-10 -
Enter the high voltage value. This
*
10 V]
analog input scaling value should
correspond to the high reference
feedback value set in
parameter 6-15 Terminal 53 High
Ref./Feedb. Value.
6-12 Terminal 53 Low Current
Range:
Function:
4 mA
[ 0 - par. 6-13
Enter the low current value. This
*
mA]
reference signal should correspond
to the low reference feedback value
set in parameter 6-14 Terminal 53
Low Ref./Feedb. Value. Set the value
M0010001
Programming Guide
6-12 Terminal 53 Low Current
Range:
6-13 Terminal 53 High Current
Range:
20 mA
*
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Size
related
*
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Size
related
*
6-16 Terminal 53 Filter Time Constant
Range:
0.005 s
*
Danfoss A/S © 10/2019 All rights reserved.
Function:
at >2 mA to activate the live zero
timeout function in
parameter 6-01 Live Zero Timeout
Function.
Function:
[ par. 6-12 -
Enter the high current value
20 mA]
corresponding to the high
reference/feedback set in
parameter 6-15 Terminal 53 High
Ref./Feedb. Value.
Function:
[-999999.999
Enter the analog input scaling value
- 999999.999 ]
that corresponds to the low
voltage/low current set in
parameter 6-10 Terminal 53 Low
Voltage and parameter 6-12 Terminal
53 Low Current.
Function:
[-999999.999
Enter the analog input scaling value
- 999999.999 ]
that corresponds to the high
voltage/high current value set in
parameter 6-11 Terminal 53 High
Voltage and parameter 6-13 Terminal
53 High Current.
Function:
NOTICE
[0.005 - 10 s]
This parameter cannot be
adjusted while the motor is
running.
Enter the filter time constant. This
constant is a first-order digital low-
pass filter time for suppressing
electrical noise in terminal 53. A
high value improves dampening
but also increases the delay
through the filter.
3
3
107