Parameter Descriptions
21-54 Ext. 3 Feedback Source
Option:
[0]
No function
*
3
3
[1]
Analog Input
53
[2]
Analog Input
54
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog Input
X30/11
[8]
Analog Input
X30/12
[9]
Analog Input
X42/1
[10]
Analog Input
X42/3
[11]
Analog Input
X42/5
[15]
Analog Input
X48/2
[16]
Analog Input
X49/1
[17]
Analog Input
X49/3
[18]
Analog Input
X49/5
[19]
Pressure 3
[20]
Pressure 4
[99]
Normal
Feedback
[100]
Bus Feedback
1
[101]
Bus Feedback
2
[102]
Bus feedback
3
[104]
Sensorless
Flow
[105]
Sensorless
Pressure
[110]
Air Pres. to
Flow
21-55 Ext. 3 Setpoint
Range:
0
ExtPID3Uni
par. 21-52
t
ExtPID3Unit]
*
196
Function:
See parameter 21-14 Ext. 1 Feedback
Source for details.
Function:
[ par. 21-51 -
See parameter 21-15 Ext. 1 Setpoint
for details.
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
HVAC Drive FC 102
21-57 Ext. 3 Reference [Unit]
Range:
0
ExtPID3Uni
t
*
21-58 Ext. 3 Feedback [Unit]
Range:
0
ExtPID3Uni
t
*
21-59 Ext. 3 Output [%]
Range:
0 %
*
3.19.7 21-6* Closed Loop 3 PID
21-60 Ext. 3 Normal/Inverse Control
Option:
[0]
*
[1]
21-61 Ext. 3 Proportional Gain
Range:
0.01
*
21-62 Ext. 3 Integral Time
Range:
10000 s
*
21-63 Ext. 3 Differentation Time
Range:
0 s
*
21-64 Ext. 3 Dif. Gain Limit
Range:
5
*
21-66 Ext. 3 On Reference Bandwidth
Range:
5 %
*
Function:
[-999999.999
See parameter 21-17 Ext. 1 Reference
- 999999.999
[Unit] for details.
ExtPID3Unit]
Function:
[-999999.999
See parameter 21-18 Ext. 1 Feedback
- 999999.999
[Unit] for details.
ExtPID3Unit]
Function:
[0 - 100 %]
See parameter 21-19 Ext. 1 Output
[%] for details.
Function:
See parameter 21-20 Ext. 1 Normal/
Inverse Control for details.
Normal
Inverse
Function:
[0 - 10 ]
See parameter 21-21 Ext. 1 Propor-
tional Gain for details.
Function:
[0.01 - 10000
See parameter 21-22 Ext. 1 Integral
s]
Time for details.
Function:
[0 - 10 s]
See parameter 21-23 Ext. 1 Differen-
tation Time for details.
Function:
[1 - 50 ]
See parameter 21-24 Ext. 1 Dif. Gain
Limit for details.
Function:
[0 - 200 %]
Enter the on-reference bandwidth.
When the PID control error (the
difference between the reference
and the feedback) is less than the
M0010001