Danfoss VLT FC 102 Programming Manual page 112

Hvac drive, software version 5.41
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Parameter Descriptions
6-46 Term. X30/12 Filter Time Constant
Range:
0.005 s
*
3
3
6-47 Term. X30/12 Live Zero
Option:
[0]
Disabled
[1]
Enabled
*
3.8.6 6-5* Analog Output 1
Parameters for configuring the scaling and limits for analog
output 1, that is terminal 42. Analog outputs are current
outputs: 0/4–20 mA. Common terminal (terminal 39) is the
same terminal and has the same electrical potential for
analog common and digital common connection.
Resolution on analog output is 12 bit.
6-50 Terminal 42 Output
Option:
110
Function:
NOTICE
[0.005 - 10 s]
This parameter cannot be
adjusted while the motor is
running.
Enter the filter time constant. This
constant is a first-order digital low-
pass filter time for suppressing
electrical noise in terminal X30/12.
A high value improves dampening
but also increases the delay
through the filter.
Function:
This parameter makes it possible to
disable the live zero-monitoring. For
example, to be used if the analog
outputs are used in a decentral I/O
system (when an analog output
does not fulfil any control function,
but feeds a data storage device).
Function:
NOTICE
Values for setting the
minimum reference are found
in open loop
parameter 3-02 Minimum
Reference and for closed loop
parameter 20-13 Minimum
Reference/Feedb.. Values for
maximum reference for open
loop are found in
parameter 3-03 Maximum
Reference and for closed loop
parameter 20-14 Maximum
Reference/Feedb.
This parameter enables the function
of terminal 42 as an analog current
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
HVAC Drive FC 102
6-50 Terminal 42 Output
Option:
[0]
[52]
[53]
[86]
[87]
[88]
[89]
[93]
[94]
[100]
[101]
[102]
[103]
[104]
[105]
[106]
[107]
[113]
[114]
[115]
Function:
output. Depending on the option
selected, the output is either 0–
20 mA or 4–20 mA. The current
value can be read out in the LCP in
parameter 16-65 Analog Output 42
[mA].
No operation
MCO 0-20mA/
0-10V
MCO 4-20mA
Pressure
Sensor 1
Pressure
Sensor 1 (4-20
mA)
Pressure
Sensor 2
Pressure
Sensor 2 (4-20
mA)
Pressure
Sensor 3
Pressure
Sensor 3 (4-20
mA)
Output freq.
0–100 Hz, (0–20 mA).
0-100
Reference
Minimum reference–Maximum
Min-Max
reference, (0–20 mA).
Feedback
-200% to +200% of
+-200%
parameter 20-14 Maximum
Reference/Feedb., (0–20 mA).
Motor cur. 0-
0–Inverter maximum current
Imax
(parameter 16-37 Inv. Max. Current),
(0-20 mA).
Torque 0-Tlim
0–Torque limit
(parameter 4-16 Torque Limit Motor
Mode), (0–20 mA).
Torque 0-
0–Motor rated torque, (0–20 mA).
Tnom
Power 0-Pnom 0–Motor rated power, (0–20 mA).
Speed 0-
0–Speed high limit
HighLim
(parameter 4-13 Motor Speed High
Limit [RPM] and
parameter 4-14 Motor Speed High
Limit [Hz]), (0–20 mA).
Ext. Closed
0–100%, (0–20 mA).
Loop 1
Ext. Closed
0–100%, (0–20 mA).
Loop 2
Ext. Closed
0–100%, (0–20 mA).
Loop 3
M0010001