Parameter Descriptions
0-25 My Personal Menu
Array [20]
Range:
Size
related
*
3
3
3.2.7 0-3* LCP Custom Readout
It is possible to customize the display elements for various
purposes:
Custom readout. Value proportional to speed
(linear, squared, or cubed depending on unit
selected in parameter 0-30 Custom Readout Unit).
Display text. Text string stored in a parameter.
Custom readout
The calculated value to be shown is based on the settings
in:
Parameter 0-30 Custom Readout Unit.
Parameter 0-31 Custom Readout Min Value (linear
only).
Parameter 0-32 Custom Readout Max Value.
Parameter 4-13 Motor Speed High Limit [RPM].
Parameter 4-14 Motor Speed High Limit [Hz].
Actual speed.
42
Function:
[0 - 9999 ]
Define up to 20 parameters to
appear in the Q1 Personal Menu,
accessible via the [Quick Menu] key
on the LCP. The parameters are
displayed in the Q1 Personal Menu
in the order they are programmed
into this array parameter. Delete
parameters by setting the value to
0000.
For example, this can be used to
provide quick, simple access to just
1 or up to 20 parameters which
require changing on a regular basis
(for example, for plant maintenance
reasons) or by an OEM to enable
simple commissioning of their
equipment.
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
HVAC Drive FC 102
Custom Readout (Value)
P 16-09
Custom Readout
Unit P 0-30
Max value
P 0-32
Min value
Linear
units only
P 0-31
Illustration 3.3 Custom Readout
The relation depends on the type of unit selected in
parameter 0-30 Custom Readout Unit:
Unit type
Dimensionless
Speed
Flow, volume
Flow, mass
Velocity
Length
Temperature
Pressure
Power
Table 3.2 Speed Relations for Different Unit Types
0-30 Custom Readout Unit
Option:
[0]
[1]
*
[5]
[10]
[11]
[12]
[20]
[21]
0
Motor Speed
High limit
P 4-13 (RPM)
P 4-14 (Hz)
Speed relation
Linear
Quadratic
Cubic
Function:
Program a value to be shown in the
LCP display. The value has a linear,
squared, or cubed relation to speed.
This relation depends on the unit
selected (see Table 3.2). The actual
calculated value can be read in
parameter 16-09 Custom Readout,
and/or shown in the display by
selecting [1609] Custom Readout in
parameter 0-20 Display Line 1.1
Small to parameter 0-24 Display Line
3 Large.
None
%
PPM
1/min
RPM
Pulse/s
l/s
l/min
Motor Speed
M0010001