Danfoss VLT FC 102 Programming Manual page 34

Hvac drive, software version 5.41
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Parameter Descriptions
0-20 Display Line 1.1 Small
Option:
[1614]
Motor current
[1615]
Frequency [%]
3
3
[1616]
Torque [Nm]
[1617]
Speed [RPM]
[1618]
Motor Thermal Thermal load on the motor,
[1619]
Thermistor
Sensor
Temperature
[1620]
Motor Angle
[1622]
Torque [%]
[1623]
Motor Shaft
Power [kW]
[1624]
Calibrated
Stator
Resistance
[1626]
Power Filtered
[kW]
[1627]
Power Filtered
[hp]
[1630]
DC Link
Voltage
[1631]
System Temp.
[1632]
Brake
Energy /s
[1633]
Brake Energy
Average
[1634]
Heatsink
Temp.
32
®
VLT
HVAC Drive FC 102
Function:
Phase current of the motor
measured as effective value.
Motor frequency, that is the output
frequency from the frequency
converter in percent. The frequency
% value is based upon the
frequency in parameter 4-19 Max
Output Frequency.
Present motor load as a percentage
of the rated motor torque.
Motor speed reference. Actual
speed depends on slip compen-
sation being used (compensation
set in parameter 1-62 Slip Compen-
sation). If not used, actual speed is
the value read in the display minus
motor slip.
calculated by the ETR function. See
also parameter group 1-9* Motor
Temperature.
Shows the actual torque produced,
in percentage.
Intermediate circuit voltage in the
frequency converter.
Present brake power transferred to
an external brake resistor.
Stated as an instantaneous value.
Brake power transferred to an
external brake resistor. The mean
power is calculated continuously for
the most recent 120 s.
Present heat sink temperature of
the frequency converter. The cut-
out limit is 95 ±5 °C; cutting back
in occurs at 70 ± 5 °C.
Danfoss A/S © 10/2019 All rights reserved.
0-20 Display Line 1.1 Small
Option:
Function:
[1635]
Inverter
Percentage load of the inverters.
Thermal
[1636]
Inv. Nom.
Nominal current of the frequency
Current
converter.
[1637]
Inv. Max.
Maximum current of the frequency
Current
converter.
[1638]
SL Controller
State of the event executed by the
State
control.
[1639]
Control Card
Temperature of the control card.
Temp.
[1642]
Service Log
Counter
[1643]
Timed Actions
See parameter group 23-0* Timed
Status
Actions.
[1645]
Motor Phase U
Current
[1646]
Motor Phase V
Current
[1647]
Motor Phase
W Current
[1650]
External
Sum of the external reference as a
Reference
percentage, that is the sum of
analog/pulse/bus.
[1652]
Feedback[Unit] Reference value from programmed
digital input(s).
[1653]
Digi Pot
View the contribution of the digital
Reference
potentiometer to the actual
reference feedback.
[1654]
Feedback 1
View the value of feedback 1. See
[Unit]
also parameter group 20-0* FC
Closed Loop.
[1655]
Feedback 2
View the value of feedback 2. See
[Unit]
also parameter group 20-0* FC
Closed Loop.
[1656]
Feedback 3
View the value of feedback 3. See
[Unit]
also parameter group 20-0* FC
Closed Loop.
[1658]
PID Output
Returns the drive closed-loop PID
[%]
controller output value in percent.
[1659]
Adjusted
Setpoint
[1660]
Digital Input
Shows the status of the digital
inputs. Signal low=0; Signal high=1.
Regarding the order, see
parameter 16-60 Digital Input. Bit 0
is at the far right.
[1661]
Terminal 53
Setting of input terminal 53.
Switch Setting
Current=0; Voltage=1.
M0010001