Danfoss VLT FC 102 Programming Manual page 18

Hvac drive, software version 5.41
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

How to Programme
[Menu] Select 1 of the following modes:
2
2
Status
Quick Setup
Main Menu
Main Menu is used for programming all parameters.
The parameters can be accessed immediately unless a
password has been created via:
Parameter 0-60 Main Menu Password,
Parameter 0-61 Access to Main Menu w/o Password,
Parameter 0-65 Personal Menu Password,
Parameter 0-66 Access to Personal Menu w/o
Password.
Quick Setup is used to set up the frequency converter
using only the most essential parameters.
The parameter values can be changed using the [
when the value is flashing.
Select Main Menu by pressing the [Menu] key a number of
times until the Main Menu LED is lit.
Select the parameter group [xx-__] and press [OK].
Select the parameter [__-xx] and press [OK].
If the parameter is an array parameter select the array
number and press [OK].
Select the wanted data value and press [OK].
Press [Back] to step backwards.
Arrow [
] [
] keys are used for manoeuvring between
parameter groups, parameters, and within parameters.
Press [OK] is used for selecting a parameter marked by the
cursor, and for enabling the change of a parameter.
Illustration 2.16 Menu Display
Operation keys
Keys for local control are found at the bottom of the
control panel.
16
®
VLT
HVAC Drive FC 102
Hand
On
Illustration 2.17 Operation Keys of the Numerical LCP (NLCP)
[Hand On] enables control of the frequency converter via
the LCP. [Hand On] also starts the motor. Press the
navigation keys [▲ ]/[▼ ]/[► ]/ [◄ ] to enter motor speed
data. The key can be selected as [1] Enable or [0] Disable
via parameter 0-40 [Hand on] Key on LCP.
External stop signals activated by control signals or a serial
bus override a start command via the LCP.
The following control signals are still active when [Hand
on] is activated:
] [
]
[Off] stops the connected motor. The key can be selected
as [1] Enable or [0] Disable via parameter 0-41 [Off] Key on
LCP.
If no external stop function is selected and the [Off] key is
inactive, the motor can be stopped by disconnecting the
mains supply.
[Auto On] enables the control terminals and/or serial
communication to control the frequency converter. When a
start signal is applied on the control terminals and/or the
bus, the frequency converter starts. The key can be
selected as [1] Enable or [0] Disable via
parameter 0-42 [Auto on] Key on LCP.
NOTICE
An active HAND-OFF-AUTO signal via the digital inputs
has higher priority than the control keys [Hand On] [Auto
On].
[Reset] is used for resetting the frequency converter after
an alarm (trip). It can be selected as [1] Enable or [0]
Disable via parameter 0-43 [Reset] Key on LCP.
Danfoss A/S © 10/2019 All rights reserved.
Auto
Off
On
[Hand On] - [Off] - [Auto On]
Reset
Coasting stop inverse
Reversing
Set-up select lsb - Set-up select msb
Stop command from serial communication
Quick stop
DC brake
Reset
M0010001