Danfoss VLT FC 102 Programming Manual page 289

Hvac drive, software version 5.41
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Troubleshooting
WARNING 47, 24 V supply low
The supply on the power card is out of range.
There are 3 supplies generated by the switch mode supply
(SMPS) on the power card:
24 V.
5 V.
±18 V.
Troubleshooting
Check for a defective power card.
WARNING 48, 1.8 V supply low
The 1.8 V DC supply used on the control card is outside of
the allowable limits. The supply is measured on the control
card.
Troubleshooting
Check for a defective control card.
If an option card is present, check for
overvoltage.
WARNING 49, Speed limit
The warning is shown when the speed is outside of the
specified range in parameter 4-11 Motor Speed Low Limit
[RPM] and parameter 4-13 Motor Speed High Limit [RPM].
When the speed is below the specified limit in
parameter 1-86 Trip Speed Low [RPM] (except when starting
or stopping), the frequency converter trips.
ALARM 50, AMA calibration failed
Contact the Danfoss supplier or Danfoss Service
Department.
ALARM 51, AMA check U
nom
The settings for motor voltage, motor current, and motor
power are wrong.
Troubleshooting
Check the settings in parameters 1-20 to 1-25.
ALARM 52, AMA low I
nom
The motor current is too low.
Troubleshooting
Check the settings in parameter 1-24 Motor
Current.
ALARM 53, AMA motor too big
The motor is too large for the AMA to operate.
ALARM 54, AMA motor too small
The motor is too small for the AMA to operate.
ALARM 55, AMA parameter out of range
The AMA cannot run because the parameter values of the
motor are outside of the acceptable range.
ALARM 56, AMA interrupted by user
The AMA is manually interrupted.
ALARM 57, AMA internal fault
Try to restart the AMA. Repeated restarts can overheat the
motor.
ALARM 58, AMA Internal fault
Contact the Danfoss supplier.
M0010001
Programming Guide
and I
nom
Danfoss A/S © 10/2019 All rights reserved.
WARNING 59, Current limit
The current is higher than the value in
parameter 4-18 Current Limit. Ensure that the motor data in
parameters 1-20 to 1-25 is set correctly. Increase the current
limit if necessary. Ensure that the system can operate safely
at a higher limit.
WARNING 60, External interlock
A digital input signal indicates a fault condition external to
the frequency converter. An external interlock has
commanded the frequency converter to trip. Clear the
external fault condition. To resume normal operation, apply
24 V DC to the terminal programmed for external interlock,
and reset the frequency converter.
WARNING 62, Output frequency at maximum limit
If the output frequency reaches the value set in
parameter 4-19 Max Output Frequency, the drive issues a
warning. The warning ceases when the output drops
below the maximum limit. If the drive is unable to limit
the frequency, it trips and issues an alarm. The latter may
happen in the flux mode if the drive loses control of the
motor.
Troubleshooting
Check the application for possible causes.
Increase the output frequency limit. Ensure that
the system can operate safely at a higher output
frequency.
WARNING 64, Voltage limit
The combination of load and speed requires a motor
voltage higher than the actual DC-link voltage.
WARNING/ALARM 65, Control card over temperature
The cutout temperature of the control card is 85 °C
(185 °F).
Troubleshooting
Check that the ambient operating temperature is
within the limits.
Check for clogged filters.
Check the fan operation.
Check the control card.
WARNING 66, Heat sink temperature low
The frequency converter is too cold to operate. This
warning is based on the temperature sensor in the IGBT
module. Increase the ambient temperature of the unit.
Also, a trickle amount of current can be supplied to the
frequency converter whenever the motor is stopped by
setting parameter 2-00 DC Hold/Preheat Current to 5% and
parameter 1-80 Function at Stop.
ALARM 67, Option module configuration has changed
One or more options have either been added or removed
since the last power-down. Check that the configuration
change is intentional and reset the unit.
4
4
287

Advertisement

Table of Contents
loading

Table of Contents