Danfoss VLT FC 102 Programming Manual page 100

Hvac drive, software version 5.41
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Parameter Descriptions
[180] Clock Fault
[181] Preventive
Maintenance
3
3
[193] Sleep Mode
[194] Broken Belt
[196] Fire Mode
[198] Drive Bypass
The below setting options are all related to the cascade
controller.
Wiring diagrams and settings for parameter, see parameter
group 25-** Cascade Pack Controller for more details.
[200] Full
Capacity
[201] Pump1
Running
[202] Pump2
Running
[203] Pump3
Running
98
VLT
The clock function has been reset to
default (2000-01-01) because of a power
failure.
1 or more of the preventive maintenance
events programmed in
parameter 23-10 Maintenance Item has
passed the time for the specified action in
parameter 23-11 Maintenance Action.
The frequency converter/system has
turned into sleep mode. See parameter
group 22-4* Sleep Mode.
A broken belt condition has been
detected. This function must be enabled
in parameter 22-60 Broken Belt Function.
The frequency converter is operating in
Fire mode. See parameter group 24-0* Fire
Mode.
To be used as signal for activating an
external electromechanical bypass,
switching the motor direct on line. See
24-1* Drive Bypass.
CAUTION
If enabling the drive bypass
function, the frequency converter is
no longer safety certified (for using
the Safe Torque Off in versions
where included).
All pumps running and at full speed.
One or more of the pumps controlled by the
cascade controller are running. The function
also depends on parameter 25-06 Number of
Pumps. If set to [0] No, Pump 1 refers to the
pump controlled by relay RELAY1 etc. If set to
[1] Yes, Pump 1 refers to the pump controlled
by the frequency converter only (without any
of the built-in relays involved), and Pump 2 to
the pump controlled by the relay RELAY1. See
Table 3.15.
See [201] Pump1 Running
See [201] Pump1 Running
Danfoss A/S © 10/2019 All rights reserved.
®
HVAC Drive FC 102
Setting in
parameter group
5-3* Digital Outputs
[200] Pump 1
Running
[201] Pump 2
Running
[203] Pump 3
Running
Table 3.15 Settings
5-30 Terminal 27 Digital Output
This parameter has the options described in chapter 3.7.10 5-3*
Digital Outputs. This parameter is active when VLT
Purpose I/O MCB 101 is mounted in the frequency converter.
Option:
[0]
*
5-31 Terminal 29 Digital Output
This parameter has the options described in chapter 3.7.10 5-3*
Digital Outputs. The default option is listed.
Option:
[0]
*
5-32 Term X30/6 Digi Out (MCB 101)
This parameter has the options described in chapter 3.7.10 5-3*
Digital Outputs. This parameter is active when VLT
Purpose I/O MCB 101 is mounted in the frequency converter.
Option:
[0]
*
5-33 Term X30/7 Digi Out (MCB 101)
Option:
[0]
No operation This parameter has the same options defined
*
3.7.11 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays.
5-40 Function Relay
Array [8]
(Relay 1 [0], Relay 2 [1]
Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]).
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Option:
[0]
Setting in parameter 25-06 Number of
Pumps
[0] No
Controlled by
Frequency converter
RELAY1
Controlled by
RELAY2
Controlled by
RELAY3
Function:
No operation
Function:
No operation
Function:
No operation
Function:
in parameter group 5-3* Digital Inputs. This
parameter is active when VLT
Purpose I/O MCB 101 is mounted in the
frequency converter.
Function:
No operation
[1] Yes
controlled
Controlled by
RELAY1
Controlled by
RELAY2
®
General
®
General
®
General
M0010001