Danfoss VLT FC 102 Programming Manual page 266

Hvac drive, software version 5.41
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Parameter Descriptions
36-26 Term. X49/3 Filter Time Constant
Range:
3
3
36-27 Term. X49/3 Live Zero
Enable live zero monitoring.
Option:
[0]
Disabled
[1]
Enabled
*
3.29.4 36-3* Analog Input X49/5
36-30 Terminal X49/5 Low Voltage
Range:
0.07 V
*
36-32 V]
36-31 Terminal X49/5 Low Current
Range:
4 mA
*
36-33 mA]
36-32 Terminal X49/5 High Voltage
Range:
10 V
*
10 V]
36-33 Terminal X49/5 High Current
Range:
20 mA
*
20 mA]
36-34 Term. X49/5 Low Ref./Feedb. Value
Range:
0
*
- 999999.999 ]
264
Function:
high value improves dampening
but also increases the delay
through the filter.
Function:
Function:
[ 0 - par.
Enter the voltage that corresponds
to the low reference value in
parameter 36-34 Term. X49/5 Low
Ref./Feedb. Value.
Function:
[ 0 - par.
Enter the current that corresponds
to the low reference value in
parameter 36-34 Term. X49/5 Low
Ref./Feedb. Value.
Function:
[ par. 36-30 -
Enter the voltage that corresponds
to the high reference value in
parameter 36-35 Term. X49/5 High
Ref./Feedb. Value.
Function:
[ par. 36-31 -
Enter the current that corresponds
to the high reference value in
parameter 36-35 Term. X49/5 High
Ref./Feedb. Value.
Function:
[-999999.999
Enter the reference or feedback
value that corresponds to the
voltage or current value in
parameter 36-20 Terminal X49/3 Low
Voltage or parameter 36-21 Terminal
X49/3 Low Current.
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
HVAC Drive FC 102
36-35 Term. X49/5 High Ref./Feedb. Value
Range:
100
*
36-36 Term. X49/5 Filter Time Constant
Range:
0.005 s
*
36-37 Term. X49/5 Live Zero
Option:
[0]
[1]
*
3.29.5 36-4* Output X49/7
Use the parameters in this group to configure the mode of
inputs and outputs of VLT
Select the functionality of terminal X49/7.
36-40 Terminal X49/7 Analogue Output
Option:
[0]
*
[52]
[86]
[88]
[93]
[100]
[101]
[102]
[103]
[104]
[105]
[106]
Function:
[-999999.999
Enter the reference or feedback
- 999999.999 ]
value that corresponds to the
voltage or current value in
parameter 36-32 Terminal X49/5 High
Voltage or parameter 36-33 Terminal
X49/5 High Current.
Function:
[0.005 - 10 s] Enter the filter time constant. This
constant is a first-order digital low-
pass filter time for suppressing
electrical noise in terminal X49/5. A
high value improves dampening
but also increases the delay
through the filter.
Function:
Disabled
Enable live zero monitoring.
Enabled
®
Programmable I/O .
Function:
No operation
MCO 0-20mA/
0-10V
Pressure
Sensor 1
Pressure
Sensor 2
Pressure
Sensor 3
Output freq.
0-100
Reference
Min-Max
Feedback
+-200%
Motor cur. 0-
Imax
Torque 0-Tlim
Torque 0-
Tnom
Power 0-Pnom
M0010001