Parameter Descriptions
0-03 Regional Settings
Option:
[0]
International
3
3
[1]
North America Sets parameter 1-21 Motor Power
0-04 Operating State at Power-up
Option:
[0]
Resume
*
[1]
Forced stop,
ref=old
0-05 Local Mode Unit
Option:
[0]
As Motor
*
Speed Unit
[1]
%
28
®
VLT
HVAC Drive FC 102
Function:
The settings not used are made
invisible.
Sets parameter 1-20 Motor Power
[kW] units to [kW] and the default
value of parameter 1-23 Motor
Frequency to 50 Hz.
[HP] units to [hp] and the default
value of parameter 1-23 Motor
Frequency to 60 Hz.
Function:
Select the operating mode after
reconnection of the frequency
converter to mains voltage after
power-down when operating in
hand-on (local) mode and in auto
mode.
Resumes operation of the
frequency converter maintaining
the same local reference and the
same start/stop condition. The
start/stop condition is applied by
[Hand On]/[Off] on the LCP or local
start via a digital input as before
the frequency converter was
powered down.
Stops the frequency converter, but
at the same time retains the local
speed reference before power-down
in the memory. After mains voltage
is reconnected and after receiving a
start command (pressing [Hand On]
or local start command via a digital
input), the frequency converter
restarts and operates at the
retained speed reference. Press
[Auto On] button on the LCP to
restart in auto mode.
Function:
Danfoss A/S © 10/2019 All rights reserved.
3.2.2 0-1* Set-up Operations
Define and control the individual parameter set-ups.
The frequency converter has 4 parameter set-ups that can
be programmed independently of each other. This makes
the frequency converter very flexible and able to meet the
requirements of many different HVAC system control
schemes, often saving the cost of external control
equipment. For example, these can be used to program
the frequency converter to operate according to 1 control
scheme in 1 set-up (for example daytime operation) and
another control scheme in another set-up (for example
night set back). Alternatively, they can be used by an AHU
or packaged unit OEM to identically program all their
factory fitted frequency converters for different equipment
models within a range to have the same parameters, and
then during production/commissioning simply select a
specific set-up depending on which model within that
range the frequency converter is installed on.
The active set-up (that is the set-up in which the frequency
converter is currently operating) can be selected in
parameter 0-10 Active Set-up and is displayed in the LCP.
Using [9] Multi set-up it is possible to switch between set-
ups with the frequency converter running or stopped, via
digital input or serial communication commands (for
example for night set back). If it is necessary to change
setups while running, ensure that parameter 0-12 This Set-
up Linked to is programmed as required. For most HVAC
applications it is not necessary to program
parameter 0-12 This Set-up Linked to even if change of set
up while running is required, but for very complex
applications, using the full flexibility of the multiple set-
ups, it may be required. Using parameter 0-11 Programming
Set-up it is possible to edit parameters within any of the
set-ups while continuing the frequency converter
operation in its active set-up which can be a different set-
up to the one being edited. Using parameter 0-51 Set-up
Copy it is possible to copy parameter settings between the
set-ups to enable quicker commissioning if similar
parameter settings are required in different set-ups.
If a set-up is changed via a fieldbus, it takes up to 5 s
before the new values are reflected via the fieldbus.
0-10 Active Set-up
Option:
Function:
Select the set-up in which the
frequency converter is to operate.
Use parameter 0-51 Set-up Copy to
copy a set-up to 1 or all other set-
ups. To avoid conflicting settings of
the same parameter within 2
different set-ups, link the set-ups
using parameter 0-12 This Set-up
Linked to. Stop the frequency
converter before switching between
set-ups where parameters marked
M0010001