Parameter Descriptions
Auto Start, the function is Auto Start. If
pressing [Off] on the LCP, the motor stops
regardless of the signals on [53] Hand Start
and [54] Auto Start.
[54] Auto start
A signal applied puts the frequency
converter into Auto mode as if [Auto On] has
been pressed. See also [53] Hand Start.
[55] DigiPot
Uses the input as an increase signal to the
Increase
digital potentiometer function described in
parameter group 3-9*.
[56] DigiPot
Uses the input as a decrease signal to the
Decrease
digital potentiometer function described in
parameter group 3-9*.
[57] DigiPot Clear
Uses the input to clear the digital potenti-
ometer reference described in parameter
group 3-9*.
[60] Counter A
(Terminal 29 or 33 only). Input for increment
(up)
counting in the SLC counter.
[61] Counter A
(Terminal 29 or 33 only). Input for
(down)
decrement counting in the SLC counter.
[62] Reset
Input for reset of counter A.
Counter A
[63] Counter B
(Terminal 29 and 33 only). Input for
(up)
increment counting in the SLC counter.
[64] Counter B
(Terminal 29 and 33 only). Input for
(down)
decrement counting in the SLC counter.
[65] Reset
Input for reset of counter B.
Counter B
[66] Sleep Mode
Forces frequency converter into Sleep mode
(see parameter group 22-4*). Reacts on the
rising edge of signal applied.
[68] Timed
Timed actions are disabled. See parameter
Actions
group 23-0* Timed Actions.
Disabled
[69] Constant OFF Timed Actions are set for Constant OFF. See
parameter group 23-0* Timed Actions.
[70] Constant ON
Timed Actions are set for Constant ON. See
parameter group 23-0* Timed Actions.
[78] Reset
Resets all data in
Preventive
parameter 16-96 Maintenance Word to 0.
Maintenance
Word
[80] PTC Card 1
All digital inputs can be set to [80] PTC Card
1. However, only 1 digital input must be set
to this option.
5-10 Terminal 18 Digital Input
The parameter contains all options and functions listed in
parameter group 5-1* Digital Inputs except for option [32] Pulse
input.
5-11 Terminal 19 Digital Input
The parameter contains all options and functions listed in
parameter group 5-1* Digital Inputs except for option [32] Pulse
input.
M0010001
Programming Guide
5–12 Terminal 27 Digital Input
Option:
[2]
Coast inverse Functions are described in parameter group
*
5-13 Terminal 29 Digital Input
Option:
[14]
Jog Functions are described under parameter group 5-1*
*
5-14 Terminal 32 Digital Input
The parameter contains all options and functions listed in
parameter group 5-1* Digital Inputs except for option [32] Pulse
input.
5-15 Terminal 33 Digital Input
The parameter contains all options and functions listed in
parameter group 5-1* Digital Inputs.
5-16 Terminal X30/2 Digital Input
Option:
[0]
No operation This parameter is active when VLT
*
5-17 Terminal X30/3 Digital Input
Option:
[0]
No operation This parameter is active when VLT
*
5-18 Terminal X30/4 Digital Input
Option:
[0]
No operation This parameter is active when VLT
*
Danfoss A/S © 10/2019 All rights reserved.
Function:
5-1* Digital Inputs.
Function:
Select the function from the available digital input
range and the additional options [60] Counter A (up),
[61] Counter A (down), [63] Counter B (up) and [64]
Counter B (down). Counters are used in smart logic
control functions.
Digital Inputs.
Function:
Purpose I/O MCB 101 is installed in the
frequency converter. The parameter contains
all options and functions listed in parameter
group 5-1* Digital Inputs except for option
[32] Pulse input.
Function:
Purpose I/O MCB 101 is installed in the
frequency converter. The parameter contains
all options and functions listed in parameter
group 5-1* Digital Inputs except for option
[32] Pulse input.
Function:
Purpose I/O MCB 101 is installed in the
frequency converter. The parameter contains
all options and functions listed in parameter
group 5-1* Digital Inputs except for option
[32] Pulse input.
3
3
®
General
®
General
®
General
89