Parameter Descriptions
8-56 Preset Reference Select
Option:
[0]
Digital input
3
3
[1]
Bus
[2]
Logic AND
[3]
Logic OR
*
3.9.7 8-7* BACnet
NOTICE
Parameters in this group are active only when
parameter 8-30 Protocol is set to [5] BACnet or [9] FC
Option when a BacNet card is installed.
8-70 BACnet Device Instance
Range:
1
*
4194302 ]
8-72 MS/TP Max Masters
Range:
127
*
8-73 MS/TP Max Info Frames
Range:
1
*
8-74 "I-Am" Service
Select whether the device should send the "I-Am" service
message only at power-up, or continuously with an interval of
approximately 1 minute.
Option:
[0]
Send at
*
power-up
[1]
Continuously
124
Function:
Select the trigger for the preset
reference selection.
A digital input triggers the preset
reference selection.
A serial communication port or the
fieldbus triggers the preset
reference selection.
The fieldbus/serial communication
port and a digital input trigger the
preset reference selection.
The fieldbus/serial communication
port or a digital input triggers the
preset reference selection.
Function:
[0 -
Enter a unique ID number for the
BACnet device.
Function:
[1 - 127 ]
Define the address of the master
which holds the highest address in
this network. Decreasing this value
optimizes polling for the token.
Function:
[1 - 65534 ]
Define how many info/data frames
the device is allowed to send while
holding the token.
Function:
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
HVAC Drive FC 102
8-75 Initialisation Password
Range:
Size
related
*
3.9.8 8-8* FC Port Diagnostics
These parameters are used for monitoring the bus
communication via the frequency converter RS485 port
terminals 68-69.
8-80 Bus Message Count
Range:
0
*
8-81 Bus Error Count
Array [6]
Range:
0
*
8-82 Slave Messages Rcvd
Range:
0
*
8-83 Slave Error Count
Range:
0
*
8-84 Slave Messages Sent
Range:
0
*
8-85 Slave Timeout Errors
Range:
0
*
Function:
[1 - 20 ]
Enter the password needed for
execution of Drive Re-initialisation
from BACnet.
Function:
[0 - 0 ]
This parameter shows the number
of valid telegrams detected on the
bus.
Function:
[0 - 0 ]
This parameter shows the number
of telegrams with faults (for
example CRC fault) detected on the
bus.
Function:
[0 - 0 ]
This parameter shows the number
of valid telegrams addressed to the
slave sent by the frequency
converter.
Function:
[0 - 0 ]
This parameter shows the number
of error telegrams, which are not
executed by the frequency
converter.
Function:
[0 - 0 ]
This parameter shows the number
of messages sent from this
frequency converter.
Function:
[0 - 0 ]
This parameter shows the number
of messages suppressed due to
timeout.