Parameter Descriptions
24-03 Fire Mode Min Reference
This parameter defines the minimum speed reference for the fire
mode to operate from, although the motor speed limits in
parameter 4-10 Motor Speed Direction has the highest priority and
limits are set. The value match the motor unit selection in
3
3
parameter 0-02 Motor Speed Unit.
Range:
Size
related
- par. 24-04
*
FireModeUnit]
24-04 Fire Mode Max Reference
This parameter defines the maximum speed reference which the
fire mode can operate to, although the motor limits in
parameter 4-10 Motor Speed Direction has the highest priority.
This maximum value is also used as reference value for the 8
preset values calculations in %.
Range:
Size
related
999999.999
*
FireModeUnit]
24-05 Fire Mode Preset Reference
A parameter array with 8 elements (0-7). The 8 present values
(zones) are for open-loop control. Index [0] is used for basic fire
mode control. Indexes 1-7 are used to enhance fire mode
control, which also overwrites the basic control. Additional
reference value can be added via parameter group 24-**.
Range:
0 %
*
100 %]
230
Function:
[ -999999.999
Minimum value for the reference/
setpoint (limiting the sum of value
in parameter 24-05 Fire Mode Preset
Reference and value of signal on
input selected in
parameter 24-06 Fire Mode Reference
Source).
If running in open loop when fire
mode is active, the unit is selected
by the setting of
parameter 0-02 Motor Speed Unit.
For closed loop, select the unit in
parameter 24-02 Fire Mode Unit.
Function:
[ par. 24-03 -
Maximum speed at which fire mode
operates. The value is used as %
calculations of the preset values.
Maximum value for the reference/
setpoint (limiting the sum of value
in parameter 24-05 Fire Mode Preset
Reference and value of signal on
input selected in
parameter 24-06 Fire Mode Reference
Source).
If running in open loop when fire
mode is active, the unit is selected
by the setting parameter 0-02 Motor
Speed Unit. For closed loop, select
the unit in parameter 24-02 Fire
Mode Unit.
Function:
[-100 -
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
HVAC Drive FC 102
24-06 Fire Mode Reference Source
Option:
[0]
*
[1]
[2]
[7]
[8]
[20]
[21]
[22]
[23]
[24]
[25]
[37]
[38]
[39]
[133]
Function:
Select the external reference input
to be used for fire mode. In open-
loop mode, this signal value is
added to the preset values in
parameter 24-05 Fire Mode Preset
Reference. There may be a different
units scaling between preset and
external values.
No function
Analog Input
53
Analog Input
54
Pulse input 29
Pulse input 33
Digital
pot.meter
Analog input
X30/11
Analog input
X30/12
Analog Input
X42/1
Analog Input
X42/3
Analog Input
X42/5
Analog Input
X49/1
Analog Input
X49/3
Analog Input
X49/5
Fieldbus REF 1 A reference value can also come via
selected fieldbus.
M0010001