Mcb 114 Sensor Input Option - Danfoss VLT FC 102 Programming Manual

Hvac drive, software version 5.41
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Parameter Lists

5.1.28 35-** MCB 114 Sensor Input Option

Paramete
Parameter description
r
number
35-0* Temp. Input Mode
35-00
Term. X48/4 Temperature Unit
35-01
Term. X48/4 Input Type
35-02
Term. X48/7 Temperature Unit
35-03
Term. X48/7 Input Type
35-04
Term. X48/10 Temperature Unit
35-05
Term. X48/10 Input Type
35-06
Temperature Sensor Alarm Function
35-1* Temp. Input X48/4
5
5
35-14
Term. X48/4 Filter Time Constant
35-15
Term. X48/4 Temp. Monitor
35-16
Term. X48/4 Low Temp. Limit
35-17
Term. X48/4 High Temp. Limit
35-2* Temp. Input X48/7
35-24
Term. X48/7 Filter Time Constant
35-25
Term. X48/7 Temp. Monitor
35-26
Term. X48/7 Low Temp. Limit
35-27
Term. X48/7 High Temp. Limit
35-3* Temp. Input X48/10
35-34
Term. X48/10 Filter Time Constant
35-35
Term. X48/10 Temp. Monitor
35-36
Term. X48/10 Low Temp. Limit
35-37
Term. X48/10 High Temp. Limit
35-4* Analog Input X48/2
35-42
Term. X48/2 Low Current
35-43
Term. X48/2 High Current
35-44
Term. X48/2 Low Ref./Feedb. Value
35-45
Term. X48/2 High Ref./Feedb. Value
35-46
Term. X48/2 Filter Time Constant
35-47
Term. X48/2 Live Zero
314
®
VLT
HVAC Drive FC 102
Default value
[60] °C
[0] Not Connected
[60] °C
[0] Not Connected
[60] °C
[0] Not Connected
[5] Stop and trip
0.005 s
[0] Disabled
ExpressionLimit
ExpressionLimit
0.005 s
[0] Disabled
ExpressionLimit
ExpressionLimit
0.005 s
[0] Disabled
ExpressionLimit
ExpressionLimit
4 mA
20 mA
0 N/A
100 N/A
0.005 s
[1] Enabled
Danfoss A/S © 10/2019 All rights reserved.
4-set-up
Change
Conver-
during
sion index
operation
All set-ups
TRUE
All set-ups
TRUE
All set-ups
TRUE
All set-ups
TRUE
All set-ups
TRUE
All set-ups
TRUE
All set-ups
TRUE
All set-ups
TRUE
-3
All set-ups
TRUE
All set-ups
TRUE
All set-ups
TRUE
All set-ups
TRUE
-3
All set-ups
TRUE
All set-ups
TRUE
All set-ups
TRUE
All set-ups
TRUE
-3
All set-ups
TRUE
All set-ups
TRUE
All set-ups
TRUE
All set-ups
TRUE
-5
All set-ups
TRUE
-5
All set-ups
TRUE
-3
All set-ups
TRUE
-3
All set-ups
TRUE
-3
All set-ups
TRUE
Type
-
Uint8
-
Uint8
-
Uint8
-
Uint8
-
Uint8
-
Uint8
-
Uint8
Uint16
-
Uint8
0
Int16
0
Int16
Uint16
-
Uint8
0
Int16
0
Int16
Uint16
-
Uint8
0
Int16
0
Int16
Int16
Int16
Int32
Int32
Uint16
-
Uint8
M0010001