Parameter Descriptions
22-32 Low Speed [RPM]
Range:
Function:
Size
[ 0 - par.
To be used if parameter 0-02 Motor
related
22-36 RPM]
Speed Unit is set to [0] RPM
*
(parameter not visible if [1] Hz is
selected).
Set used speed for the 50% level.
This function is used for storing
values necessary for tuning no-flow
detection.
22-33 Low Speed [Hz]
Range:
Function:
Size
[ 0 - par.
To be used if parameter 0-02 Motor
related
22-37 Hz]
Speed Unit is set for [1] Hz
*
(parameter not visible if [0] RPM is
selected).
Set used speed for the 50% level.
The function is used for storing
values necessary for tuning no-flow
detection.
22-34 Low Speed Power [kW]
Range:
Function:
Size
[ 0 - 5.50 kW] To be used if
related
parameter 0-03 Regional Settings is
*
set for [0] International (parameter
not visible if [1] North America is
selected).
Set power consumption at 50%
speed level.
This function is used for storing
values necessary for tuning no-flow
detection.
22-35 Low Speed Power [HP]
Range:
Function:
Size
[ 0 - 7.50 hp]
To be used if
related
parameter 0-03 Regional Settings is
*
set for [1] North America (parameter
not visible if [0] International is
selected).
Set power consumption at 50%
speed level.
This function is used for storing
values necessary for tuning no-flow
detection.
22-36 High Speed [RPM]
Range:
Function:
Size
[ 0 - par. 4-13
To be used if parameter 0-02 Motor
related
RPM]
Speed Unit is set for [0] RPM
*
(parameter not visible if [1] Hz is
selected).
Set used speed for the 85% level.
M0010001
Programming Guide
22-36 High Speed [RPM]
Range:
22-37 High Speed [Hz]
Range:
Size
related
*
22-38 High Speed Power [kW]
Range:
Size
related
*
22-39 High Speed Power [HP]
Range:
Size
related
*
Danfoss A/S © 10/2019 All rights reserved.
Function:
The function is used for storing
values necessary for tuning no-flow
detection.
Function:
[ 0 - par. 4-14
To be used if parameter 0-02 Motor
Hz]
Speed Unit is set for [1] Hz
(parameter not visible if [0] RPM is
selected).
Set used speed for the 85% level.
The function is used for storing
values necessary for tuning no-flow
detection.
Function:
[ 0 - 5.50 kW] To be used, if
parameter 0-03 Regional Settings is
set for [0] International (parameter
not visible if [1] North America is
selected).
Set power consumption at 85%
speed level.
This function is used for storing
values necessary for tuning no-flow
detection.
Function:
[ 0 - 7.50 hp]
To be used if
parameter 0-03 Regional Settings is
set for [1] North America (parameter
not visible if [0] International is
selected).
Set power consumption at 85%
speed level.
This function is used for storing
values necessary for tuning no-flow
detection.
3