Parameter Descriptions
26-42 Terminal X42/7 Max. Scale
Range:
100 %
*
3
3
26-43 Terminal X42/7 Bus Control
Range:
0 %
*
26-44 Terminal X42/7 Timeout Preset
Range:
0 %
*
3.24.6 26-5* Analog Out X42/9
Parameters for configuring the scaling and output function
for analog output, terminal X42/9.
26-50 Terminal X42/9 Output
Option:
[0]
No operation
*
[52]
MCO 0-20mA/
0-10V
[86]
Pressure
Sensor 1
[88]
Pressure
Sensor 2
254
Function:
[0 - 200 %]
Scale the maximum output of the
selected analog signal at terminal
X42/7. Set the value to the
maximum value of the voltage
signal output. Scale the output to
give a voltage lower than 10 V at
full scale; or 10 V at an output
below 100% of the maximum signal
value. If 10 V is the required output
current at a value between 0–100%
of the full-scale output, program
the percentage value in the
parameter, that is 50%=10 V. If a
voltage 0–10 V is required at
maximum output, calculate the
percentage as follows:
10V
desired maximum voltage
that is
10V
5V :  
  ×  100 %   =  200 %
5V
See Illustration 3.31.
Function:
[0 - 100 %]
Holds the level of terminal X42/7 if
controlled by bus.
Function:
[0 - 100 %]
Holds the preset level of terminal
X42/7.
If a fieldbus and a timeout function
are selected in
parameter 26-50 Terminal X42/9
Output, the output presets to this
level.
Function:
Set the function of terminal X42/9.
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
HVAC Drive FC 102
26-50 Terminal X42/9 Output
Option:
[93]
[100]
[101]
[102]
[103]
[104]
 x 100 %
[105]
[106]
[107]
[113]
[114]
[115]
[121]
[139]
[141]
[186]
26-51 Terminal X42/9 Min. Scale
For more information, see parameter 6-51 Terminal 42 Output Min
Scale.
Range:
0 %
*
Function:
Pressure
Sensor 3
Output freq.
0–100 Hz, (0–10 V).
0-100
Reference
Minimum reference–maximum
Min-Max
reference, (0–10 V).
Feedback
-200% to +200% of
+-200%
parameter 3-03 Maximum Reference,
(0–10 V).
Motor cur. 0-
0–inverter maximum current
Imax
(parameter 16-37 Inv. Max. Current),
(0–10 V).
Torque 0-Tlim
0–torque limit
(parameter 4-16 Torque Limit Motor
Mode), (0–10 V).
Torque 0-
0–motor rated torque, (0–10 V).
Tnom
Power 0-Pnom 0–motor rated power, (0–10 V).
Speed 0-
0–speed high limit
HighLim
(parameter 4-13 Motor Speed High
Limit [RPM] and
parameter 4-14 Motor Speed High
Limit [Hz]), (0–10 V).
Ext. Closed
0–100%, (0–10 V).
Loop 1
Ext. Closed
0–100%, (0–10 V).
Loop 2
Ext. Closed
0–100%, (0–10 V).
Loop 3
Air pres. to
Flow
Bus ctrl.
0–100%, (0–10 V).
Bus ctrl t.o.
0–100%, (0–10 V).
Pressure
Sensor 4
Function:
[0 - 200 %]
Scale the minimum output of the
selected analog signal at terminal
X42/9 as a percentage of the
maximum signal level. For example,
if 0 V is required at 25% of the
maximum output value, program
25%. Scaling values up to 100% can
never be higher than the
corresponding setting in
parameter 26-52 Terminal X42/9 Max.
Scale.
M0010001