248 Technical data
Frame
ACH580-01-
size
3-phase U 1 = 440...480 V, P n at U n = 480 V, 60 Hz
R1
02A1-4...012A-4
R2
014A-4...023A-4
R3
027A-4...044A-4
R4
052A-4...065A-4
R4
077A-4
R5
078A-4...096A-4
R6
124A-4
R7
156A-4...180A-4
R8
240A-4...260A-4
R9
302A-4
R9
361A-4...414A-4
3-phase U 1 = 500...600 V, P n at U n = 575 V, 60 Hz
R2
02A7-6...017A-6
R3
022A-6...032A-6
R5
041A-6...077A-6
R7
099A-6...125A-6
R8
144A-6
R9
192A-6
R9
242A-6
R9
271A-6
Switching frequency derating with actual output current values
These tables show the output current values with different switching frequencies. Note
that other derating factors, for example ambient temperature and altitude, may also
affect to the output current.
IEC
Frame
ACH580-
size
01-
3-phase U n = 230 V
R1
04A7-2
R1
06A7-2
R1
07A6-2
R1
012A-2
Derating factor (k) for the minimum switching frequen-
1 kHz
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Nominal
Nominal output current (I 2 ) for the minimum switching fre-
output
I 2
1 kHz
A
A
4.7
4.7
6.7
6.7
7.6
7.6
12.0
12.0
cies at 40 °C (+104 °F)
2 kHz
4 kHz
1
1
1
1
1
1
1
1
1
1
1
1
0.97
0.84
0.98
0.89
0.96
0.82
1
1
0.95
0.79
1
1
1
1
1
1
1
1
1
1
1
1
1
0.83
1
0.74
quencies at 40 °C (+104 °F)
2 kHz
4 kHz
A
A
4.7
4.7
6.7
6.7
7.6
7.6
12.0
12.0
8 kHz
12 kHz
0.67
0.65
0.65
0.82
0.73
0.71
0.66
0.71
0.61
0.58
0.58
0.72
0.74
0.70
0.66
0.66
0.66
0.66
0.66
8 kHz
12 kHz
A
A
4.2
3.8
6.0
5.4
6.8
6.1
10.7
9.6
0.50
0.48
0.48
0.64
0.55
0.57
0.52
0.53
0.45
0.43
0.43
0.54
0.50
0.51
0.50
0.50
0.50
0.50
0.50
16 kHz
A
3.4
4.8
5.5
8.6