YASKAWA Sigma-V Series User Manual page 84

Ac servo drives
Hide thumbs Also See for Sigma-V Series:
Table of Contents

Advertisement

3 Wiring and Connection
3.4.2 Output Signal Allocations
(3) Example of Output Signal Allocation
The procedure to set Rotation Detection (/TGON) signal of factory setting to
Interlock (/BK) signal is shown below.
Step
1
2
3
4
5
6
7
8
9
10
11
(4) Checking Output Signals
Output signal status can be checked using the output signal monitor (Un006). As for the output signal monitor
(Un006), refer to 8.5 Monitoring Output Signals.
3-36
Pn50E
Pn50F
Display after
Operation
MODE/SET
MODE/SET
MODE/SET
MODE/SET
Display flashes.
MODE/SET
MODE/SET
MODE/SET
MODE/SET
MODE/SET
Display flashes.
MODE/SET
To enable the change in the setting, turn the power OFF and ON again.
Before
After
Keys
Press the MODE/SET Key to select the parameter setting.
If a parameter other than Pn50E is displayed, press the UP
or DOWN Key to select Pn50E.
DATA/
Press the DATA/SHIFT Key for approximately one second
to display the current data of Pn50E.
(/TGON is allocated on CN1-27 (28).)
DATA/
Press the DATA/SHIFT Key to select the third digit from
the right. Press the DOWN Key to set "0."
(Sets /TGON "Invalid.")
DATA/
Press the MODE/SET Key.
The data flashes and is saved.
DATA/
Press the DATA/SHIFT Key for approximately one second
to return to the display Pn50E.
DATA/
Press the UP Key to display Pn50F.
DATA/
Press the DATA/SHIFT Key for approximately one second
to display the current data of Pn50F.
(/BK is set to "Invalid.")
DATA/
Press the DATA/SHIFT Key to select the third digit from
the right. Press the UP Key to set "2."
(Allocates /BK to CN1-27 (28).)
DATA/
Press the MODE/SET Key.
The value flashes and is saved.
DATA/
Press the DATA/SHIFT Key for approximately one second
to return to the display Pn50F. /TGON is set as "Invalid"
and /BK is allocated on CN1-27 (28).
DATA/
Invalid
and allocate Brake
"
"
Operation