Setting Example
If the servomotor moves 0.2 μm for every pulse of position reference, the external encoder sine wave pitch is
20 μm, and the number of divisions is 256, the electronic gear ratio will be as follow.
Electronic gear ratio
Therefore, set 512 for Pn20E (numerator B) and 200 for Pn210 (denominator A).

9.3.6 Alarm Detection

The setting of alarm detection (Pn51B/Pn52A) is shown below.
(1) Excessive Error Level between Servomotor and Load Positions (Pn51B)
This setting detects the difference between the feedback position of the motor encoder and the feedback load
position of the external encoder in fully-closed loop control. If the detected difference is above the set level,
the motor-load position error overflow alarm (A.d10) will be output.
Excessive Error Level between Servomotor and
Load Positions
Pn51B
Setting Range
0 to 1073741824
Note: When Pn51B is set to 0, the motor-load position error overflow alarm (A.d10) is not detected.
(2) Multiplier per One Fully-closed Rotation (Pn52A)
The coefficient of the error between the external encoder and the motor per motor rotation can be set. This
function can be used to prevent the motor from running out of control due to damage to the external encoder or
to detect slippage of the belt.
Setting Example
Increase the value if the belt slips or is twisted excessively.
If the set value is 0, the external encoder value will be read as it is.
If the factory setting of 20 is used, the second rotation will start with the error for the first motor rotation mul-
tiplied by 0.8. (Refer to the following figure.)
Error between motor and external encoder
Small
Related Parameter
Multiplier per One Fully-closed Rotation
Pn52A
Setting Range
0 to 100
B
Pn20E
0.2 × 256
= =
=
A
Pn210
20
Setting Unit
1 reference unit
Big
Less than
one rotation
rotation
Setting Unit
1%
9.3 Parameter Settings for Fully-closed Loop Control
512
Rotation
=
200
Position
Factory Setting
1000
Number of motor rotations
1st
2nd
rotation
Position
Factory Setting
20
Classifica-
tion
When Enabled
Immediately
Setup
Pn52A=0
Pn52A=20
Pn52A=100
Rotation
3rd
rotation
Classifica-
tion
When Enabled
Immediately
Setup
9
9-21