(2) Manual Adjustment of Reference Offset (Fn00A)
This method adjusts the offset inputting the amount of reference offset directly.
Use the manual adjustment of the reference offset (Fn00A) in the following cases:
• To adjust the position error to zero when a position loop is formed with the host controller and the servomo-
tor is stopped by servolock.
• To deliberately set the offset amount to some value.
• To check the offset amount set in the automatic adjustment mode of reference offset.
Note: The adjusted value is not initialized by executing the Fn005 function (Initializing Parameter Settings).
Preparation
The following conditions must be met to adjust the offsets of speed reference manually.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The main circuit power supply must be ON. (Refer to 5.10.4.)
Operating Procedure
Adjust the reference offset manually with the panel operator using the following steps.
Display after
Step
Operation
1
2
3
4
5
6
(Example)
7
8
Keys
Press the MODE/SET Key to select the utility function.
MODE/SET
DATA/
Press the UP or the DOWN Key to select Fn00A.
MODE/SET
DATA/
Press the DATA/SHIFT Key for approximately one second.
The display shown on the left appears.
Note: When "no_oP" flashes for approximately one second,
the write prohibited setting has been set in Fn010.
MODE/SET
DATA/
Change the setting in Fn010 and press the key again
to enable writing. (Refer to 7.12.)
Turn ON the servo ON signal (/S-ON) from an external
device. The display shown on the left appears.
Press the DATA/SHIFT Key for approximately one second.
The present offset amount is displayed.
MODE/SET
DATA/
Press the UP or the DOWN Key to stop the motor. The dis-
played value is the amount of the offset after adjustment.
MODE/SET
DATA/
Press the MODE/SET Key. After "donE" flashes for
approximately one second, the display shown on the left
appears.
MODE/SET
DATA/
Press the DATA/SHIFT Key for approximately one second.
"Fn00A" is displayed again.
MODE/SET
DATA/
5.3 Speed Control
Operation
5
5-25